background image

Power-Flo Pumps & Systems • 877-24PUMPS • www.powerflopumps.com
ISP No. pfext ISP - 1/2021

Part 

Number

Capacity Connection

Max 

Temp

Pre-

Charge

Max Working 

Pressure

Wt.

lbs

PFEXT2H

2 gal

1/2” NPT

240° F

12 PSI

100 PSI

5

PFEXT4H

4 gal

1/2” NPT

240° F

12 PSI

100 PSI

9

PFEXT8H

8 gal

1/2” NPT

240° F

12 PSI

100 PSI

14

PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY

INSTALLER: LEAVE THIS MANUAL WITH THE END USER

 READ CAREFULLY THE PRODUCT 

 INSTALLATION, OPERATING AND 

MAINTENANCE INSTRUCTIONS. FAILURE TO FOLLOW THE 

INSTRUCTIONS AND WARNINGS IN THE MANUAL MAY 

RESULT IN SERIOUS OR FATAL INJURY AND/OR PROPERTY 

DAMAGE, AND WILL VOID THE PRODUCT WARRANTY. 

THIS PRODUCT MUST BE INSTALLED BY A QUALIFIED 

PROFESSIONAL. FOLLOW ALL APPLICABLE LOCAL AND 

STATE CODES AND REGULATIONS, IN THE ABSENCE OF 

SUCH CODES, FOLLOW THE CURRENT EDITIONS OF THE 

NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC 

CODE, AS APPLICABLE.

This is the safety alter symbol. It is used to alert you 

to potential personal injury and other hazards. Obey 

all safety messages that follow this symbol to reduce 

the risk possible injury as well as property damage.

NOTE:

 Inspect for shipping damage and notify carrier or store 

where purchased immediately if damage is present. To avoid 

risk of personal injury and property damage, if the product

appears to be malfunctioning or shows signs of corrosion, 

call a qualified professional immediately. Use proper safety 

equipment when installing.

 FAILURE TO PROPERLY SEAL VALVE CAP 

 WILL RESULT IN LOSS OF PRECHARGE 

CAUSING PRODUCT TO FAIL.

 This product, like most products under 

 pressure, may over time corrode, weaken, 

burst or explode, causing serious or fatal personal injury, 

leaking or flooding and/or property damage. To minimize risk, 

a licensed professional must install and periodically inspect and 

services the product. A drop pan connected to an adequate 

drain must be installed if leaking or flowing could cause 

property damage. Do not locate in an area where leaking could 

cause property damage to the area adjacent to the appliance 

or to lower floors of the structure.

EXPLOSION OF RUPTURE HAZARD.

 A relief valve must 

be installed to prevent pressure in excess of local code 

requirement or maximum working pressure designated in the 

Product Manual, whichever is less. 

Do not expose product to 

freezing temperatures or temperatures in excel of 240°F.

 Do 

not adjust the pre-charge or re-charge this product except for

any adjustments at the time of the initial installation, especially 

if product is corroded, damaged or with diminished integrity. 

Adjustments to pre-charge must be done at ambient 

temperature only. Failure to properly size the product or follow 

these instructions may result in excess strain on the system 

and may lead to product failure, serious or fatal personal injury, 

leakage, and/or property damage.

 Mount vertically only. Do not mount on 

 dead-end pipe.

FOR USE IN CLOSED HYDRONIC SYSTEMS ONLY:

 Do not 

install for domestic water systems, or in open heating systems. 

Corrosion and tank failure may result.

Pre-Installation

1. Visually inspect the tank for any damage.

2. Adjust pre-charge to equal system fill pressure.

3. Replace and tighten plastic cap on air fitting.

Installation

1. Drain the boiler system or isolate the area where the tank will 

be installed.

2. Install the tank on the supply side of the boiler, on the 

suction –side of the heating circulator(s) (see Figure 1).

3. Once the tank is installed, re-pressurize the system and check 

for leaks. Repair as necessary.

4. Restart the boiler system and check for relief valve discharge. 

If the relief valve drips, the tank may be improperly charged or 

undersized.

5. The tank is now operational and will absorb expanded water 

during boiler operation.

PFEXT - Power-Flo Expansion Tanks