3.4.2.2 Output characteristics
Property
Value Unit
Number of outputs
16
Max. continuous output DC per pin
1 A
Max. total continuous
output current per byte
4 A
Power dissipation
per pin at 24 V for 0.5 A
0.20 W
Power dissipation
per pin at 24 V for 1.5 A
0.45 W
Output ON delay (typical)
100
μ
s
Output OFF delay (typical)
200
μ
s
Watchdog (max.)
64 ms
Short circuit output DC
0.7 - 2.5 A
Delay time current limitation (max.)
2 ms
Isolation
by opto coupler
Output ON display
LED
External connection
1 terminal block for 8 outputs
All outputs are referenced against 0 V (power supply connector X30,
pin 3).