Parameter number
Parameter
Description
Unit
Factory set
ting
Heating
circuit 1
Heating
circuit 2
Heating
circuit 3
850
1150
1450
Floor curing
function
Controlled screed-drying function:
Off : The function is inoperative.
Curing/functional heating : Active for 7 days,
3 days at 25°C and 4 days at 55°C.
Curing heating : Active for 18 days, 6 days
from 25°C to 55°C increasing by 5°C a day,
6 days at 55°C, 6 days from 55°C to 25°C
diminishing by 5°C a day.
Functional/curing heating : "Functional Heat
ing" cycle first, and then "Ready for
Occupation".
Functional heating : "Curing Mode"
cycle first, and then "Heating Functional".
Manually : Regulation is based on the
"Manual Control Drying" set point.
S
Off
851
1151
1451
Floor curing setp
manually
The flow temperature set point of the "Manual"
controlled drying function can be set separately
for each heating circuit.
°C
25
855
1155
1455
Floor curing setp
current
Displays the current day of the controlled
screed-drying function. With ‘ ---‘ the function is
deactivated.
-
‘---’
856
1156
1456
Days
complete.current
Displays the current flow temperature set point
of the controlled screed-drying function. With
‘---‘ the function is deactivated.
-
‘---’
Tab.47 Menu Temps / mode hot water
Parameter
number
Parameter
Description
Factory setting
1600
Operating mode
Off: Permanent running at the frost-protection set point.
On : Domestic hot water loading is done automatically at the
nominal set point.
Eco : The temperature maintenance function is deactivated.
On
1610
Hot water temp
setpoint
DHW set point during release times
60°C
1612
Reduced temp
setpoint
Reduced set point outside release times
35°C
1620
Release
Start-up enabled:
Time hot water : This setting provides domestic hot water
production with a dedicated timer program.
Time setting central heating : The release of domestic hot
water is done with the same timer program as the heating circuits.
24h/day : Default setting for instantaneous boilers.
Time hot water
1640
Legionella function
Off
Periodically
Fixed weekday
Off
1641
Legionella funct
periodically
Determines after how many days the anti-legionella function
must be reactivated.
7
1642
Legionella funct
weekday
Determines on which day the anti-legionella function must be
activated.
Monday
1644
Legionella funct time Determines the start-up time of the anti-legionella function
(Hours / Minutes).
– –/– –
1660
Circulating pump
release
The circulating pump is tripped during the release time:
Time central heating CH3
Hot water release
Time hot water
Time auxiliary
Hot water release
9 Settings
70
Sirius Two FS
7609493 - v03 - 08122014
Summary of Contents for Sirius two FS 110
Page 16: ......
Page 34: ... MW 1000007 03 1 MW 1000008 03 2 ...
Page 35: ... MW 3000122 01 3 MW 1000010 05 4 MW 3000025 01 5 5 ...
Page 52: ... ...
Page 61: ... ...
Page 101: ... MW 3000127 03 5 5 MW 3000128 02 6 7 MW 3000107 01 7 A B ...
Page 102: ... MW 3000182 02 8 8 MW 3000108 04 9 9 10 MW 3000109 04 ...
Page 104: ...21 0 1 12 1 1 1 0 1 12 1 1 1 0 1 1 1 1 1 1 1 0 1 1 1 1 1 2 MW 3000103 L2 2 ...
Page 107: ... 7 MW 3000111 03 ...
Page 109: ...0 0 0 7 MW 3000111 03 0 ...
Page 112: ...0 0 0 0 0 0 0 00 0 0 ...
Page 114: ... ...
Page 115: ... ...
Page 116: ...7609493 v03 08122014 7609493 001 03 www pottertoncommercial co uk ...