
Caution
When the flue pipes are dis-assembled, new seals must be used
for the reassembly!
6.3.5 Outlets
Note
When codes of practice dictate the use of a terminal guard use a
suitable guard of stainless steel construction. There must be a
clearance of at least 50 mm between any part of the terminal and
the guard.
Fig.16 Outlets
AD-3000707-01
N
I
I
G
F
M
I
A
A
F
H
J,K
D
E
H
Likely flue positions requiring a flue terminal guard
C
R
A
I
J,K
I
L
S
B
T
U
Tab.12 Terminal position with minimum distance
Directly below an opening, air brick, opening windows, etc.
300 mm
Above an opening, air brick, opening window etc.
300 mm
C
Horizontally to an opening, air brick, opening window etc.
300 mm
D
Below gutters, soil pipes or drain pipes.
25 (75) mm
Below eaves.
25 (200) mm
Below balconies or car port roof.
25 (200) mm
G
From a vertical drain pipe or soil pipe.
25 (150) mm
H
From an internal or external corner.
25 (300) mm
I
Above ground, roof or balcony level.
300 mm
J
From a surface or boundary line facing a terminal.
600 mm
K
From a terminal facing a terminal (Horizontal flue).
From a terminal facing a terminal (Vertical flue).
1200 mm
600 mm
L
From an opening in carport (e.g. door, window) into the dwelling.
1200 mm
M
Vertically from a terminal on the same wall.
1500 mm
N
Horizontally from a terminal on the same wall.
300 mm
R
From adjacent wall to flue (vertical only).
300 mm
S
From an adjacent opening window (vertical only).
1000 mm
T
Adjacent to windows or openings on pitched and flat roofs.
600 mm
6 Installation
40
Paramount four 30 – 115 kW
7658013 - 02 - 15092016