5.3 Choice of the location
5.3.1 Requirements for the installation room
The installation room must be dry and frost-free.
Warning
Changes to conducts for combustion air and flue gas are only al
lowed after consultation a qualified installer. Such changes in
clude:
Making the set-up location smaller
Retrofitting joint-sealed windows and outside doors
Sealing windows and outside doors
Covering or removing supply air apertures
Covering chimneys
Note
There are inspection apertures for the chimney sweep in the flue
gas spigot on top of the boiler. Ensure that these inspection aper
tures are always accessible.
5.3.2 Notes for installation location
Caution
Danger of damage from water!
The following must be observed when installing the Paramount
four:
In order to prevent damage due to water, particularly due to leak
ages in the DHW storage tank, suitable precautionary measures
should be taken regarding installation.
Installation room
The installation room must be dry and frost-free.
The installation location has to be selected particularly with respect to
the routing of the flue gas pipes. When installing the boiler, the specified
wall clearances have to be maintained.
Along with the general rules of the technology, especially the regulations
of the federal German states, such as fire and construction ordinances
as well as heating room guidelines, must be observed. There should be
sufficient space in front of the equipment to carry out inspection and
maintenance work.
Caution
Risk of damage to the device!
Aggressive foreign substances in the combustion supply air can
destroy or damage the heat generator. Therefore the installation in
rooms with heavy dust accumulation is only allowed with
room air independent operating modes.
If the Paramount four is operated in rooms in which solvents,
cleaning agents containing chlorine, paints, glues or similar sub
stances are worked with or in which such substances are stored,
only room air independent operation is permissible. This applies
especially for rooms in which ammonia and its compounds are
heavily used, as well as nitrites and sulphides (animal breeding
and recycling facilities, battery and galvanising rooms, etc.).
During the installation of the Paramount four under these condi
tions DIN 50929 (Corrosion probability of metallic materials with
external corrosion loading) as well as information sheet i. 158;
“German Copper Institute” is heeded.
For damages occurring due to the installation in an unsuitable location or
based on improper combustion air supply, no warranty claims may be
made.