Caution
The temperatures at certain collectors cannot be measured cor
rectly if the pump is switched off. For this reason, the pump must
be activated from time to time.
Min run time collector pump (3831)
The collector pump is periodically switched on for the running time set
here.
Collector start function on (3832) and Collector start function
off (3833)
The time when the collector start function starts or stops is set here.
Collector start funct grad (3834)
As soon as there is a temperature increase on the collector sensor, the
collector pump switches on. The higher the value selected here, the great
er the temperature rise must be.
Collector frost protection (3840)
In order to prevent freezing of the collector, the collector pump will be acti
vated in case of frost danger.
Collector overtemp prot (3850)
In case of overheating danger, charging of the storage tank is continued in
order to remove heat. When the storage tank safety temperature has been
reached, charging of the storage tank will be interrupted.
Evaporation heat carrier (3860)
Pump protecting function, to prevent overheating of the collector pump in
case of evaporating danger of the heat carrying medium due to high col
lector temperature.
Pump speed min (3870) andPump speed max (3871)
Input of the minimum and maximum solar circuit pump speeds in percent.
Antifreeze (3880)
Information of the antifreeze used.
Antifreeze concentration (3881)
Input of antifreeze concentration for usage measurement of solar energy.
Pump capacity (3884)
Input of the flow of the installed pump for calculation of the brought in vol
ume for usage measurement.
Pulse unit yield (3887)
Defines the flow per pulse for the Hx input. The Hx input must be config
ured to pulse count for this.
9.2.14 Solid fuel boiler
Locks other heat sources (4102)
If the solid fuel boiler is activated, other heat generators, e.g. oil./gas boil
ers, are blocked as soon as an increase in the boiler temperature is estab
lished that indicates that the comparative temperature has been exceeded
(prog. no. 4133).
Setpoint min (4110)
The boiler pump is only put into operation if the boiler temperature has
reached the minimum setpoint set here in addition to the necessary tem
perature difference.