PFC-3002T

Fire  Alarm  Control  Panel

INSTALLATION and OPERATION MANUAL

©2004  by  Potter  Electric  Signal  Company           

November  2004

LT-514POT  REV.0

firealarmresources.com

Summary of Contents for PFC-3002T

Page 1: ...ions contained in this manual are subject to change without prior notice by the manufacturer PFC 3002T Fire Alarm Control Panel INSTALLATION and OPERATION MANUAL 2004 by Potter Electric Signal Company...

Page 2: ...firealarmresources com...

Page 3: ...t LED 3 Signal Trouble LED 3 Sequence of Operation 4 Normal 4 Alarm 4 Signal Silence 4 Reset Lamp Test 4 System Checkout 4 Power up and Troubleshooting 4 Wiring Tables and Information 8 Appendix A Com...

Page 4: ...etails 5 Figure 2 Circuit Board Layout 6 Figure 3 Detection and signal wiring 7 Figure 4 Wiring table for detection zone 8 Figure 5 Wiring table for bells and horns 8 Figure 6 Alarm and trouble relay...

Page 5: ...nsions Surface Mounting 1 Mark the location of the four mounting holes 2 Install the top two screws into the wall and place the panel over the screws 3 Install the bottom screws and tighten down all f...

Page 6: ...available for bells and horns providing 1 7A of signal power Refer to Figure 3 on page 7 for wiring instruction and to Figure 5 page 8 on for wire size Alarm and Trouble Relays Alarm and trouble relay...

Page 7: ...illuminate steadily and the buzzer will sound Buzzer Buzzer Silence Switch The buzzer will sound intermittently for any trouble For any alarm in the system the buzzer will sound steadily Operating th...

Page 8: ...preform a lamp test as well as reset the panel System Checkout Before turning the power on 1 Check all external wiring for opens shorts or grounds 2 Check that transformer cables are securely connecte...

Page 9: ...5 Figure 1 Backbox and flush trim mounting details 13 3 4 12 3 4 1 11 16 Optional flush mounting trim model FA 102TR 7 32 dia mounting hole 2 7 8 7 1 8 1 1 4 10 3 8 firealarmresources com...

Page 10: ...C ON TRBL SIG SIL BATT GND TRANSFORMER P1 P2 P3 BATTERY P4 SIG 1 F1 2A BATTERY A C 2A F2 COM JW2 JW1 1 TB2 2 TRBL ALARM ZONE 1 TRBL ALARM ZONE 2 AUX TRBL ON DSW1 DIP SWITCHES 1 8 MD 733 DETECTION ZONE...

Page 11: ...ctor Bell F F S R Alarm threshold current is 21 mA Maximum loop resistance is 100 ohms ELR 3 9K 1 2W F S R TB2 Detection zone 1 F F ELR 3 9K 1 2W Signal zone Detection zone 2 22VDC 3mA STBY 5mV ripple...

Page 12: ...hould not exceed 100 ohms Total Signal Load Maximum Wiring Run to Last Device ELR Max Loop Resistance 18AWG 16AWG 14AWG 12AWG 0hms Amperes ft m ft m ft m ft m Ohms 0 06 2350 716 3750 1143 6000 1829 85...

Page 13: ...ommon alarm relay contacts 28VDC 3A resistive Common trouble relay contacts 28VDC 3A resistive Cut JW3 for N O Cut JW4 for N C N O C N C TS2 TRL TRB A C ON 24V 24VDC 250 mA max 24VDC 50 mA max unsuper...

Page 14: ...003 1400 A PSD 7131 70 201000 005 2400 A Mirtone PSD 7130 70 201000 001 1451 A B401B 73471 PSD 7130 70 201000 002 1451 A B406B 73494 PSD 7130 70 201000 003 2451 A B401B 73575 PSD 7130 70 201000 005 24...

Page 15: ...Compatibility Identifier Head Base Rated Standby Current System Sensor Sentrol ESL 1100 A N A 0 12 mA 429C S10A N A 0 10 mA 1151 B110LP A A 0 12 mA 429CT S10A N A 0 10 mA 1151 B116LP A A 0 12 mA 429CS...

Page 16: ...A N A 0 12 mA 2400AT A N A 0 12 mA Detection Systems Inc 2400AIT A N A 0 12 mA DS250 B N A 0 10 mA 2451 B401B A A 0 12 mA DS250TH B N A 0 10 mA 2451 B406B A A 0 12 mA DS282 B N A 0 10 mA 2451 DH400 A...

Page 17: ...FR RSS 2415W FR RSS 241575W FR RSS 2430W FR RSS 2475W FR RSS 24110W FR RSS 2415C FW RSS 2430C FW RSS 2475C FW RSS 24100C FW MT 12 24 ULC MT 24 LS VFR ULC MT 24 WS VFR ULC AMT 12 24 R ULC AMT 24 LS VF...

Page 18: ...ICE The main AC branch circuit connection for the Fire Alarm Control Unit must provide a dedicated continuous power without provision of any disconnect devices Use 12 AWG wire with 600 volt insulation...

Page 19: ...e shall not be responsible to repair or replace equipment which has been repaired by others abused improperly installed altered or otherwise misused or damaged in any way Unless previously contracted...

Page 20: ...firealarmresources com...