PAD300-IB
SLC Voltage
24 VDC
SLC Standby / Alarm Current (*)
150 μA
Active Current (LED ON)
4.5 mA
Installation Temp Range
32oF to 150oF
Operating Humidity Range
0% - 93% (Non-condensing)
Dimension
Φ 6.4 in
Weight
6.88 oz
Height
1.57 in
*Standby current is the current the device consumes when the device
is in a non-activated condition and where no communication current
is transmitted to the fire alarm control panel.
PAD300-IB
Contents
A.
Introduction
D.
Wiring
B.
Specifications
E.
Locking Feature
C.
Mounting
F.
Warranty
The PAD300-IB is an isolator base. It will open the
Signaling Line Circuit downstream when short circuit is
detected. This will provide devices between the control
panel and the isolator to continue to operate.
The PAD300-IB is a mounting base designed to work
specially with the PAD300 series detectors. Compatible
detectors include PAD300-PD, PAD300-HD,PAD300-
PHD.
Each base includes one (1) LED which is off in normal
condition. The short is indicated by a steady red LED
and once the short is removed the unit will return to
normal operation.
For further information, please refer to the control panel
installation instructions.
Refer to the company website for the latest revision of
this manual.
B. Specifications
A. Introduction
C. Mounting
Mounting Options:
PAD300-IB can be mounted on a single gang, 3-1/2” octagon, 3-1/2”
square, double gang, 4” octagon, 4” square, 50mm c/c, 60mm c/c and
70mm c/c boxes.
Terminal Layout:
Mounting Instructions:
1. Loosen screws on junction box or leave screws in place.
2. Align keyholes on the mounting plate with screw heads.
3. Slide screws to the slot on the mounting plate.
4. Tighten screws to secure mounting plate.
5. Plug base and turn clockwise to secure in place.Tighten screws
to secure base on mounting plate.
Mounting plate
Screw
Isolation Contacts:
SLC2+/SLC2-
SLC+/SLC-
1609 Park 370 Pl, Hazelwood, MO 63042
www.pottersignal.com
Specifications / Ratings for detector base only:
DETECTORS ARE NOT TO BE USED WITH
DETECTOR GUARDS UNLESS THE COMBINATION HAS BEEN
EVALUATED AND FOUND SUITABLE FOR THAT PURPOSE.