background image

MKT. #8830003 - REV A

3/11

PRINTED IN USA

PAGE 1 OF 3

MOM-4

MOnitOred Output MOdule

Potter Electric Signal Company, LLC • St. Louis, MO • Cust Service: 866-956-1211 • Tech Support: 866-240-1870 • Canada: 888-882-1833

 

• www.pottersignal.com

SLC loop wiring (signal line circuit) is power limited. Power supply 

for terminals 24+ and 24- must be power limited, so that the wiring 

for terminals OUT+, OUT- is power-limited. All terminals should be 

wired in accordance with the requirements of NFPA 70 (NEC) and 

NFPA 72 (National Fire Alarm Code). Failure to follow the wiring 

diagrams in the following pages will cause the system to not operate 

as  intended.  For  further  information,  refer  to  the  control  panel 

installation instructions.

There  is  a  possibility  that  the  relay  in  MOM-4  module  has  been 

accidentally  set  to  "latched"  position  during  shipment.  THE 

SIGNAL  LINE  CIRCUIT  (SLC)  MUST  BE  CONNECTED 

BEFORE  CONNECTING  24VDC.  If  power  is  applied  to  the 

terminals 24+ and 24- and the relay is latched, a short circuit of 

wires connected to terminals OUT+, OUT- may damage the module. 

If this should occur, the performance of the Addressable Module 

must be verified.

For more information refer to 5403556, PFC-8060/8500 Installation, 

Operation and Programming Manual. 

description

The MOM-4 module provides a programmable source of power to 

control and operate output devices including notification appliances 

and releasing devices. Additionally, it continuously supervises wiring 

connected to terminals OUT+, OUT- for open or short circuits and 24+ 

and 24- when 24VDC is applied. 

MOM-4 employs one red LED to indicate the status. In normal condi-

tion, the LED flashes. When the output is activated, the LED will turn 

on constantly. In case of trouble, the LED will turn off.

Since the system allows maximum 13 LEDs on devices to turn on 

constantly, if system already has 13 lighted LEDs on devices, MOM-

4 will not turn on the LED and keep flashing even if the output of 

MOM-4 is activated.

installation

 Figure : Installation into the compatible electrical box

Features

24 VDC Monitored Output Control

• 

5.1k ohm EOL

• 

NAC or Releasing Control

• 

LED indicates activation of module

• 

All terminals are power limited

• 

Listed with Potter/Amseco®, Gentex®, & Cooper Wheelock® 

• 

sync modules and devices

Reviews: