background image

LED-16 Series

LED Annunciator

8830096 - Rev D

   •   

12/18

 page 1 OF 2

Potter Electric Signal Company, LLC

      •   

 St. Louis, MO

      •   

 Phone: 800-325-3936 

      •   

 www.pottersignal.com

LED-16 Flush Mount

LED-16 Surface Mount

Description

The LeD-16 Series is a LeD remote annunciator for various potter 

addressable  fire  control  panels.  The  LED-16  Series  communicates 

using a RS-485 (P-Link) connection to the main panel providing zone 

specific indication of Alarm, Supervisory, Trouble conditions.

The LeD-16 Series features 2 slide-in labels allowing each of the 16 

zones to be customized for any application. It can be flush mounted 

or surface mounted. It can be mounted on a single gang electrical box 

or a four-square electrical box. The annunciator utilizes a sheet metal 

enclosure secured with a Potter lock.

Technical Specifications

Standby Current

20 ma

Alarm Current

25 ma

Operating Temperature

0°C-49°C (32°F-120°F) 

Operating Humidity Range 0 to 93% (non-condensing)
Maximum Wire Length

6500 ft.

Maximum Annunciators

31

Flush Mount Size 

(WxHxD)

11 3/8” x 9-1/4” x 7/8”

Surface Mount Size 

(WxHxD)

11 3/8” x 9-1/4” x 3 1/8”

Wire Gauge

12 AWG-22 AWG

Compatible Panels

IPA Series

AFC/ARC Series

PFC-4064

p-Series*

PFC-6000 Addressable Series*

*Legacy Product

Features

• 

Capable of displaying alarms, supervisory, trouble status for 16 

zones

• 

System Silence and Reset buttons

• 

Common LEDs for status indication

• 

Maximum 31 LED-16s for:
PFC-6800, P400(R), IPA-4000, and AFC-1000.

• 

Maximum 10 LED-16s for:
PFC-6030/6075(R)/6200, P100/200/300, IPA-60, IPA-100, AFC-

50, AFC/ARC-100 and PFC-4064

• 

Maximum P-Link wire length of 6,500 feet

• 

available in four colors

• 

Product includes a 5 year warranty

• 

UUKL Listed for Smoke Control

NOTE: 

LED PWR can be provided by any fire listed source. Output 

power must be 16 VDC–33 VDC and must be power limited.

7305-0328:0200 UOXX.S2930