20
Set up
The connection between the charger and energy
manager is established directly from the charger and
in the Web Application of the energy manager.
Establishing a connection to the charger
The
ENERGY MANAGER
indicator light shows the
status of the connection to the PLC network and to
the energy manager.
PLC/energy manager connection status indicator
Status display
Meaning
Pulsing yellow
Status 1
The charger attempts
to re-establish the pre-
viously used PLC con-
nection (maximum du-
ration: 60 seconds).
e
Optional:
Press and hold the
MULTI-FUNCTION
BUTTON
for 3 sec-
onds to skip recon-
nection.
The charger then
searches for a new
PLC network.
Flashing yellow
Status 2
The charger attempts
to establish a connec-
tion to the new PLC
network (maximum du-
ration: 9 minutes).
Status display
Meaning
Pulsing white
Status 3
PLC connection is es-
tablished. A connection
is being established to
the last known energy
manager.
e
Optional:
Press and hold the
MULTI-FUNCTION
BUTTON
for 3 sec-
onds to skip recon-
nection.
Flashing white
Status 4
PLC connection is es-
tablished. Connection
to a new energy man-
ager is established.
Lights up green
Status 5
The energy manager
has been successfully
connected.
Lights up red
Status 6
Connection could not
be established.
Ensuring good connection quality of the
PLC network
To ensure a sufficient transmission rate for PLC com-
munication, the following measures should be taken
into account during electrical installation:
e
If a PLC connection is not possible, test the Por-
sche charger in a different wall socket.
e
Keep the distance between consumers with PLC
functionality low. As a test, the connection to the
PLC modem can be made at an electrical socket
near the PLC modem (e.g. in the living room). If
a connection is established here, but does not
subsequently work in the garage, this may be
due to the distance being too great. Please note
the following information on phase assignment.
e
Route the VDSL cable at a distance of at least
10 cm to the power lines and electrical sockets.
e
Preferably establish the PCL connection via the
same current phase.
–
If the charger is connected using a single-
phase plug, the external PLC modem should
be connected to the same phase as the
charger in the case of a multi-phase domes-
tic connection.
–
If the charger is connected using a multi-
phase plug, the external PLC modem should
be connected to phase L1.
e
Check whether other electrical devices are caus-
ing interference. For this purpose, disconnect
other devices from the mains supply and check
the PLC connection. Possible sources of inter-
ference may be, for example, dimmers, halogen
lighting systems, fridges and freezers, switched-
mode power supplies, dryers, washing machines
and electric pumps in operation.