- 38 -
Example : Swimming pool water is at 20°C, heat pump is working for 5 minutes in heating boost (Hi) mode, and the
needle indicates 20 bars / 280 PSI / 32 °C / 90 °F.
→
32°C
– 20 °C = 12°C
→
by-pass setting is correct (between 10 and 15°C)
Abnormal pressure
If the pressure is too high or too low, it indicates that the water flow circulating inside the heat pump is not correct.
You need to adjust the water flow by opening or closing the by-pass valve. Open little by little it if the pressure is too low
and close it little by little if the pressure is too high until it remains stable in the correct area.
When heat pump is stopped the temperature indicated by the needle should be close to water temperature.
If the value is 0, don’t start the machine (contact your seller).
Frequency of settings
The optimum water flow through the pool heat pump depends mainly on the water temperature and to a lesser extent
on the ambient air temperature.
Ideally the settings should be done:
•
When the pool heat pump is turned on and water is cold.
•
When the pool temperature is increasing.
•
When the desired water temperature is reached.
Thereafter the flow does not need to be regulated any further. Simply check the pressure once in a while to ensure that
the pool heat pump is working normally and that the water flow hasn't changed.
Winter setting
When you are winterizing your pool system, you must:
•
Turn the pool heat pump off
•
Close downstream and upstream valves of the by-pass system.
•
Drain the exchanger to prevent any risk of freezing.
•
Open completely the downstream and upstream valves to empty the heat exchanger tank before closing them.
•
Cover the heat pump with a water-proof cover.
A special cover designed for each heat pump model can be provided as an option.
Summary of Contents for EcoSpec 09 Silent Inverter
Page 1: ...Handbook EcoSpec Silent Inverter 21 0 FR GB docx EcoSpec Silent Inverter FR...
Page 13: ...13 R glages cran Luminosit et langues des messages d erreur Informations Informations cran...
Page 21: ...21 EcoSpec Silent Inverter EN...
Page 33: ...33 Screen setting Luminosity and error messages language Informations Informations screen...
Page 41: ...41 EcoSpec Silent Inverter ES...
Page 53: ...53 Ajuste pantalla Iluminaci n mensajes de error idioma Informaci n Informaci n pantalla...
Page 61: ...61 EcoSpec Silent Inverter DE...