POLA HP17 Handbook Download Page 1

HP17

SL 3.1

Thermostat with alarm

Handbook

INSTALLATION

How to connect the line
Connect 230V line on terminals L-N.
Protect supply with adequate fuse.

How to connect the contacts
Connect terminals  on the  terminal  block (contacts up to 4AMP.AC1).

*1

 Other power voltage

   if you required.

HP17

SX TEMPERATURE

PROBE

HEAT CONTACT

COOL CONTACT

ALARM

N.O. CONTACT 

*2

ALARM

N.C. CONTACT 

*2

230V LINE 

*1

As it company policy to continually improve the products the Manufacturers
reserve the right to make any modifications thereto without prior notice. They
cannot be held liable for any damage due to malfunction.

07.01.13

*2

 Alarm relay de excited or excited in normal condition referring to Cost, function rY.AL.

PRESET PROGRAMS (Bootstrap)

At delivery this processor is programmed with  the  following (variable) settings.
To return to these settings at any time.
Power off the processor, press ALARM MAX key and keep it pressed giving
power on: release ALARM MAX key when on the screen boot message
appears.    t.SEt = 25.0°    AL _ _ = 10.0°   AL - - = 30.0°

The COSt  values are shown in COSt Programming.

Press  +

: will be displayed followed by
°Maximum Temperature Recording.

Press  -  :

will be displayed followed by
°Minimum Temperature Recording.

VIEWING TEMPERATURE RECORDING

Values recorder are memory permanent stored: for memory clear keep pushed  +  keys
for more than 3 seconds:  CLEA  message will be composed on display before clearing
operation.

MAIN SETTING (Run Mode)

TEMPERATURE SETTING
Press TEMP (key lamp flashes): this message will be displayed
instead of the ° Set temperature value .
Press  +  or  -  to modify, press SET  to escape.

MINIMUM ALARM TEMPERATURE
Press MIN ALARM (key lamp flashes): this message will be
displayed instead of the ° Set  Minimum temperature value .
Press  +  or  -  to modify (*), press ALARM MIN  to escape.

TEMPERATURE SETTING
Press MAX ALARM (key lamp flashes): this message will be
displayed instead of the ° Set Maximum temperature value .
Press  +  or  -  to modify (*), press ALARM MAX  to escape.

* If option o.ALA=1  (see COSt)  the c.AL_ or  c.AL-   message appears on display.
  If option o.ALA=2  (see COSt)  the r.AL_ or  r.AL-   message appears on display.

How to connect the sensors
Connect the sensor provided as shown  in  the  diagram.  For  remote  connections
use  a standard 0.5-square millimeter two-pole wire
, taking great care   over  the
connections,  by insulating and sealing the joins carefully. -O.C.-  is displayed when the
temperature sensor wiring is open,  -S.C.-  is displayed when the temperature sensor
wiring is short circuit.