37
The regulator cooperates only with an
exhaust temperature sensor type CT2S.
In order to inspect the sensor, it is
necessary to use a very precise
multimeter – otherwise, the sensor can
only be checked roughly.
CT4
Temp.
°C
Min.
Ω
Nom.
Ω
Max.
Ω
0
802
815
828
10
874
886
898
20
950
961
972
25
990
1000
1010
30
1029
1040
1051
40
1108
1122
1136
50
1192
1209
1225
60
1278
1299
1319
70
1369
1392
1416
80
1462
1490
1518
90
1559
1591
1623
100
1659
1696
1733
CT4-P
Temp.
°C
Min.
Ω
Nom.
Ω
Max.
Ω
-30
609
624
638
-20
669
684
698
-10
733
747
761
0
802
815
828
10
874
886
898
20
950
961
972
CT2S
Temp.
°C
Min.
Ω
Nom.
Ω
Max.
Ω
0
999,7
1000,0
1000,3
25
1096,9
1097,3
1097,7
50
1193,4
1194,0
1194,6
100
1384,2
1385,0
1385,8
125
1478,5
1479,4
1480,3
150
1572,0
1573,1
1574,2
13.7
Connecting room thermostat
for mixer circuits
Room
thermostats
connected
to
executive module B as per influences
mixer 1 and mixer 2 circuits. If the entire
building heating system is fed by the
mixer circuit, all room thermostat
settings for boiler should be disabled.
After opening of the contacts, the room
thermostat decreases the preset mixer
circuit temperature by the value of
preset mixer temperature decrease from
thermostat. This parameter can be found
in:
Mixer 1 settings > Mixer room
therm.
The value of this parameter should be
chosen in such a way, that after
activation of room thermostat (opening
of contacts), the temperature in the
room decreased.
13.8
Connecting reserve boiler
The regulator can control operation of a
reserve (gas or oil) boiler. In such case it
is not necessary to activate and
deactivate the boiler manually. Reserve
boiler
will
be
activated
when
temperature of the biomass boiler drops
and
deactivated
if
appropriate
temperature of the biomass boiler is
reached. Only a qualified installer is
allowed to connect a reserve (e.g. gas)
boiler. Such operation should be
executed in accordance with technical
documentation of this boiler.
Connecting a reserve boiler eliminates a
possibility of connecting alarm signalling.
Reserve boiler should be connected to
87-88 terminals through a relay in
accordance with the figure below.