Turn minimum rate adjustment screw to set required burner pressure (minimum fire). Pressure
is increased by turning clockwise (pressure regulator models), or decreased by turning
counterclockwise: LPG 0.62kPa, NG 0.37kPa
Warning!
You should never connect any device adapted to the combustion of liquefied gas to the gas network of
natural gas and vice versa
.
•
Pressure reading
o
Unscrew gas valve box cover using cross screwdriver.
o
Take off the cover.