Turn MANUAL knob and main valve knob to the ON position.
o
Turn pressure regulator adjustment screw to set required burner pressure (high fire). Pressure is
increased by turning clockwise (pressure regulator models), or decreased by turning
counterclockwise: LPG 1kPa, NG 0.81kPa
o
After adjustment, replace the plug.
o
If no other adjustments are required, close pressure tap(s) by turning the screw(s) full clockwise.
Check all connections/pressure tap(s) for leaks.
o
If the desired outlet pressure or flow cannot be achieved by adjusting the gas valve, check the
gas valve inlet pressure using a manometer at the valve inlet pressure tap. If the inlet pressure is
in the normal range, replace the gas valve; otherwise, take necessary steps to assure proper gas
pressure to the valve
•
Minimum rate Adjustment
o
Connect a pressure manometer to the valve outlet pressure tap. Pressure tap is opened by
turning the screw counterclockwise. Minimum rate adjustment screw is located on the top of
the metal valve body.