8-Port IP Power Manager 

 

IPM-8001 

IPM-8002

 

User’s Manual 

 

 

 

Summary of Contents for 8-Port IP Power Manager IPM-8001

Page 1: ...8 Port IP Power Manager IPM 8001 IPM 8002 User s Manual ...

Page 2: ...limits for a Class B digital device pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no gua...

Page 3: ...tellite Earth Station Equipment As of April 8 2000 Safety This equipment is designed with the utmost care for the safety of those who install and use it However special attention must be paid to the dangers of electric shock and static electricity when working with electrical equipment All guidelines of this and of the computer manufacture must therefore be allowed at all times to ensure the safe ...

Page 4: ...CONNECTING INPUT POWER 6 2 2 CONNECTING OUTPUT DEVICE 6 2 3 CONNECTING DIGITAL OUTPUTS 7 2 4 CONNECTING EMD 7 2 5 CONNECTING THE CONSOLE 8 2 6 CONNECTING LAN OR WAN 8 CHAPTER 3 USER CONTROL BUTTON 1 CHAPTER 4 QUICK SETUP 2 CHAPTER 5 CONFIGURE WITH CONSOLE 5 5 1 RUN HYPER TERMINAL 5 5 2 IP POWER MANAGER CONFIGURATION 8 5 2 1 System Group 8 5 2 2 Control Group 9 5 3 OUTLETS CONTROL 10 5 4 ACCESS CON...

Page 5: ...uration 23 6 3 2 Multi User 24 6 3 3 Date Time 26 6 3 4 Trap Receivers 27 6 3 6 WOL 28 6 3 7 Email Notification 29 6 3 8 External Links 30 6 4 NETWORK 31 6 4 1 Configuration 31 6 4 2 Control 32 6 4 3 Access Control 33 6 5 LOGS 34 6 5 1 History 34 6 5 2 Event 35 6 5 3 Clear and Save Log Data 36 CHAPTER 7 UTILITY 38 APPENDIX A ERROR CODE 40 APPENDIX B SPECIFICATION 41 APPENDIX C GLOSSARY 42 ...

Page 6: ...input power range from 220V to 240VAC in the following section unless specified IPM 8000 will means the IP Power Manager of the two models 1 3 Features z Eight power outlets that can be turn on or off in multiple ways with easy monitoring of current consumption z Versatile sensors supported through EMD Environmental Monitoring Device inputs z Active extended devices via digital outputs z Monitor a...

Page 7: ...le users with password protection for double layer security z Address specific IP security masks to prevent unauthorized access z Available in 110V 220V and 240V models 1 4 Front and Rear Panel Front Panel IPM 8001 Rear Panel IPM 8002 Rear Panel 1 5 LED And Button on Front Panel 1 5 1 Power Outlet LED and Button 2 There are eight set of LED and button for each power outlet the description is as be...

Page 8: ...n Power on 3 Remote control indicator Displays the remote control status of each outlet Off Remote control is enabled Red Remote control is disabled Button Description A Allows manual control of each power outlet Press repeatedly to switch between remote control and power on off mode 1 5 2 System Load and Status Indication 3 For IPM 8000 the INPUT LEDs and STATUS digital LED indicators shows the r...

Page 9: ...nction Description STATUS Input power status indicator Displays input voltage Volts input current Ampere and frequency Hz sequentially on the 7 segment switching display This indicator also shows system errors in the form of an error code such E01 E02 E03 and so on You may check to Appendix A Error Code to know the details of each error code 4 1 6 Front Panel Interface ...

Page 10: ...onnect an optional EMD to this port Dip Switch Operation mode DIP switch Sets the mode of operation for the IP Power Manager S1 off and S2 off Normal operation default mode Please don t change the position of the dip switches it may cause your IP Power Manager works incorrect when the dip switches in wrong position Reset Reset button Enables you to reset the IP Power Manager in case the system loc...

Page 11: ... Manager 8000 to your LAN or WAN If it shows E16 that is mean the power phase of connected power outlet is reverse Please try to make the power phase correct Or you can refer to section 5 2 2 to disable Input Phase Detection on IP Power Manager temporally For other error message please refer to Appendix A Error Code for details 2 2 Connecting Output Device 6 The IP Power Manager has eight power ou...

Page 12: ...provide power to the connected device So the connected device should connect with its power adapter You can control the digital outputs remotely through the console or over the LAN 2 4 Connecting EMD 7 An environmental monitoring device that is sensors connected to for detecting temperature humidity water level and so on can be connected to the IP Power Manager with the console port The EMD can al...

Page 13: ...own Then you can run Hyper Terminal to control and manage your IP Power Manager 2 6 Connecting LAN or WAN 8 The IP Power Manager has an RJ 45 LAN connector that enables you to monitor and manage the power outlets and digital outputs over the network The IP Power Manager has a graphic user interface that allows you to control the device through a web browser Connect the IP Power Manager to a free p...

Page 14: ...he IP Power Manager from your PC or laptop When the network has installed a router you can also use your mobile phone or PDA that is web browser supported and connected to Internet to control IP Power Manager 9 ...

Page 15: ...n once The remote control indicator starts flashing red 2 Now press control button again within 5 seconds and hold for more than 5 seconds The remote control indicator starts flashing red at a faster speed and then inverts its original state For instance if remote control indicator is enabled gray before you press the control button it turns on red after step 2 indicating that remote control is di...

Page 16: ...ility hyper link to initiate the installation If the autorun program is not process in your PC you can click the Start button and choose Run Suppose E is your CD ROM drive When the dialog box appears enter E Utility Setup exe and press enter key You will see the dialog box as below 3 Please press Discover to find out your IP Power Manager 2 4 Please select your IP Power Manager in the Device List ...

Page 17: ...button then you will see a dialog box asking you the user name and password Please enter admin for first time configuration If you have change the user name and password please enter correct user name and password of this dialog box Please press OK 3 7 Then the IP Power Manager configuration web page will appear You can check the power outlet status in this web page For more configurations please ...

Page 18: ... 4 ...

Page 19: ...nd configure its settings such as its IP address outlet control parameters access control table and trap receivers table 5 1 Run Hyper Terminal Follow these steps to start HyperTerminal and communicate with the IP Power Manager 1 To start HyperTerminal click Star Programs Accessories Communications HyperT erminal from the Windows Start button 2 A New Connection opens Type a name for the connection...

Page 20: ...Make sure that the Bits per second field is set to 9600 Click OK when done 6 5 Press any key The IP Power Manager Configuration Utility Main menu opens and you are prompted for a password Type the default password admin and press Enter to continue The main menu options are displayed ...

Page 21: ... 7 6 After enter correct password you will see the main menu of console interface ...

Page 22: ...ss of IP Power Manager is dotted format Default value is 192 168 0 10 and size is 15 characters Gateway Address The IP address of the gateway is dotted format Default value is 0 0 0 0 and size is 15 characters Network Mask The subnet mask of IP Power Manager is dotted format Default value is 255 255 255 0 and size is 15 characters System Date Set date of IP Power Manager format is dd mm yyyy Syste...

Page 23: ... when this option enabled Ping Echo Control Enable Disable the IP Power Manager to respond to Ping requests For protect IP Power Manager when they are connect to Internet We will suggest you enable this option to let your IP Power Manager stop response the ping command Input Phase Detection IP Power Manager will detect the input power phase to make sure the connected device can receive the correct...

Page 24: ...nection with the IP Power Manager The user may configure the SNMP protocol to use a port number other than the standard SNMP port 161 5 3 Outlets Control In this option you can select the power outlet and change its settings Please select the power outlet you want to configure in above screen Then the below screen will appear 10 Option Description Outlet Name Set the name of this outlet Location S...

Page 25: ...network access to the IP Power Manager There are 2 kinds of type for Access Type Permitted and Denied It is need to set the first item for its IP Address to 255 255 255 255 and Access Type to Permitted as default value in order to let user is able to connect to the IP Power Manager Option Description IP Address The management station s IP address 0 0 0 0 means entry not configured e g An entry 192...

Page 26: ... String The community string of the trap PDU to be sent The maximum length of the string is 19 characters NMS Type Types of the traps to be received Set the type of the trap NMS Severity Description Set the level of the trap to be received Information All traps are received Warning Trap that need to be noticed and are in dangerous is received Severe The significant traps such as the outlet voltage...

Page 27: ...on To Default When you would like to reset IP Power Manger to default configuration please select this option and press y 5 7 Restart IP Power Manager After configuration please select this option to make the new function works ...

Page 28: ... 14 5 8 Exit Select this option to exit Hyper Terminal ...

Page 29: ... your desktop laptop PDA or even your mobile phone This section provides instructions about how to use the web interface to configure and control the IP Power Manager remotely 1 Open your web browser 2 Enter the IP address of your IP Power Manager in the address field 3 A User Name and Password dialog box will appear Please enter your User Name and Password here Default User Name and Password are ...

Page 30: ... 6 1 Power Management 6 1 1 Control This page shows the rear view of IP Power Manager While mouse moving over the picture of input each outlets or digital output it will link to its associated page If the security level for each outlet is Read or the remote control status is Disabled the link of outlet will be disabled the color of outlet picture will be gray You can power on off all the power out...

Page 31: ...The current input voltage in Volt Input Current Amp The current input currents in Amp Input Frequency Hz The current input frequency in Hz Input Voltage Threshold High Volt High threshold of input voltage When input voltage is higher than this value IP Power Manager will take action specified in the Inlet Events Action table ...

Page 32: ...nput voltage over high set point Input Voltage Under Threshold Low Turn off selected outlets or digital outputs will occur when the input voltage under low set point 6 1 1 2 Outlets This page shows the outlet status and allows user to configure the settings 18 Option Description Status Output Current Amp The nominal input currents in Amp Power Status When the power status is Off the color is Red I...

Page 33: ...let immediately by click the buttons 6 1 1 3 Digital Outputs This page shows the digital output status and allows user to configure the settings 19 Option Description Status Digital Output 1 The status of digital output 1 while system start up Digital Output 2 The status of digital output 2 while system start up Event Action Digital Output 1 Event Action If selected the digital output 1 will inver...

Page 34: ...ase press Add New Then you will see the screen below When Edit button click you will also see this screen for edit the existing schedule If you want to delete the schedule please press Delete button 20 Option Description Schedule Type Choose the schedule type to be Weekly Schedule or Special Schedule Schedule Day Set the week day of the schedule if the Schedule Type is Weekly Schedule Set the spec...

Page 35: ...ime 21 6 2 Environment When the console port connected with the EMD the web interface will shows this option for environment monitoring and setting If the IP Power Manager does not connect with the EMD the web interface will not show this setup option 6 2 1 Status This page shows the temperature humidity and alarms information of the EMD Environmental Monitoring Device If there is alarm occurred t...

Page 36: ...he user can configure the humidity offset as 2 so the sensor can then adjust its final value to 45 Alarm Type If an alarm sensor water leak security etc is connected to the IP Power Manager the user can configure the alarm as Disabled Normal Open or Normal Close A Disabled setting will mean the alarm is inactive Normal Open and Normal Close are used for a two wire detector that will emulate an ope...

Page 37: ...rm This page allows user to modify the parameters associated with the environment events 6 3 System 6 3 1 Configuration This page contains three groups Configure System Administrator Name and Password and Control group Configuration of this page is allowed when the security level is Administrator ...

Page 38: ...vel community of SNMP or to view the current setting Size is 31 characters History Log Interval This field allows the user to set the polling time in seconds of the Input Output and EMD if connected information The readings will be stored in the history log Administrator User Name and Password Administrator User Name You may enter the administrator user name and the default value is admin Size is ...

Page 39: ...ssword which is used to log in the IP Power Manager system Outlet Privilege The security level for each outlet There are two kinds of security level one is Read Write and the other is Read Modify Clicking on the Add New or Edit button will pop up Multi User Editor window which could configure the setting of schedule Clicking on the Delete button will remove an existence user 25 ...

Page 40: ...is dd mm yyyy IP Power Manager System Time Current time of the IP Power Manager format is hh mm ss Configure Date and Time Set Manually User can set the date and time with the following format dd mm yyyy and hh mm ss Synchronize with computer time Select this option and click Set Value to synchronize with the time from the computer clock Synchronize with NTP server You must configure the NTP serve...

Page 41: ...ap PDU to be sent The maximum length of the string is 19 characters Trap Type Types of the traps to be received Set the type of the trap None Traps are not be received IP Power Manager Trap Traps are received base on IP Power Manager MIB Severity Set the level of the trap to be received Information All traps are received Warning Trap that need to be noticed and are in dangerous is received Severe ...

Page 42: ...d next WOL packet Index The index number of the entry in the table MAC Address MAC address of the PC you would like to wake up Action You can select Enable or Disable this option Outlet Define Please select one of the outlet or keep the default setting Description Customer description string Modify You can press Edit to modify the MAC table or press Delete to delete the MAC address table Wake On L...

Page 43: ...ss you entered User Account As Administrator you may enter the User Account of the mail server that will be used by the IP Power Manager to login mail server to forward mails User Password As Administrator you may enter the User Password of User Account Sender s Email Address This field specify the content of the From field of the Email If this field left blank the sender s address will be account...

Page 44: ...Manager in csv format suitable for viewing in Microsoft Excel One attachment contains the History Log contents Logged IP Power Manager data and the other contains the Event Log contents Logged Event text Selecting Events Status specifies that the recipient should receive an email message containing the event related notification and the two file attachments as described above each time an event no...

Page 45: ...nected in URL format Status There are two kinds of status Enabled and Disabled If the setting is Enabled the screen text will be shown on the main menu frame 31 6 4 Network 6 4 1 Configuration Configuration of this page is allowed when the security level is Administrator If user reset configurations to default the configuration of IP Address Gateway Address and Subnet Mask will also be kept ...

Page 46: ...ield will contain 0 0 0 0 6 4 2 Control Configuration of this page is allowed when the security level is Administrator It allows user to change some network ports and enabled or disabled the function of protocols 32 Option Description BootP DHCP Status This is the parameter enabling or disabling the Boot Protocol BootP Dynamic Host Configuration Protocol DHCP process These protocols are used to ob...

Page 47: ...ol to use a port number other than the standard SNMP port 161 6 4 3 Access Control Configuration of this page is allowed when the security level is Administrator It prevents unauthorized network access to the IP Power Manager There are 2 kinds of type for Access Type Permitted and Denied It is need to set the first item for its IP Address to 255 255 255 255 and Access Type to Permitted as default ...

Page 48: ...ers The Administrator can change consolidation interval by modifying the variable History Log Interval in Configuration of IP Power Manager page The existing values are overwritten when the maximum number of entries rows has been reached You can clear the log data in Clear Save menu 6 5 1 History You will see the history log list in this screen You may select one of them to check the log content I...

Page 49: ...ecording Input Frequency This shows the input voltage in Hz at the time of recording Total Output Current This shows the total output current in Amps at the time of recording Output Current This shows the output current of the 8 outlets in Amps at the time of recording EMD Temperature This shows the temperature in o C at the time of recording EMD Humidity This shows the humidity in at the time of ...

Page 50: ... column show the date on which the recording was made Time hh mm ss This gives the time in a 24 hour format when the values were recorded Event Description 36 6 5 3 Clear and Save Log Data This screen allows you to clear or save the log file ...

Page 51: ...Option Description Clear Log Data Please select which log you would like to delete and click Clear button Save Log Data You can click the diskette icon to save History or Event log into a file 37 ...

Page 52: ...P Power Manager is not appear in the list you can add this device to the list manually Modify You may press this button to enter the default login user name and password of your IP Power Manager Before some operating of this utility you will need to enter the default login user name and password firstly Remove Remove IP Power Manager from the list Discover When your IP Power Manger is not in the l...

Page 53: ... 39 with the located firmware Open Press this button to locate the firmware Quit Close utility ...

Page 54: ...rent over threshold Amp E07 Outlet C current over threshold Amp E08 Outlet D current over threshold Amp E09 Outlet E current over threshold Amp E10 Outlet F current over threshold Amp E11 Outlet G current over threshold Amp E12 Outlet H current over threshold Amp E13 Input source abnormal for 110V model E14 Input source abnormal for 220 240V model E15 Input current sensor value abnormal E16 Input ...

Page 55: ...0Hz 240V 13A 50 60Hz Load 15A for each outlet 10A for each outlet or total 15A 10A for each outlet or total 13A Inlet Connector 1 x IEC 320 C20 Outlet Connector 8 x NEMA 5 15R 8 x IEC 320 C13 Management Tool Web Browser SNMP software Windows base utility Telnet Hyper Terminal via console Dimension 436 x 270 x 44 mm L x W x H Weight 3 8Kg Model IPM EMD Input Relay Two digital inputs Connection RJ 4...

Page 56: ...s to exchange information Host Name The name given to a computer or client station that acts as a source for information on the network HTTP HTTP HyperText Transport Protocol is the communications protocol used to connect to servers on the World Wide Web HTTP establishes a connection with a Web server and transmits HTML pages to client browser for example Windows IE HTTP addresses all begin with t...

Page 57: ... Internet primary and secondary servers synchronize to Coordinated Universal Time UTC Packet A packet is a portion of data that is transmitted in network communications Packets are also sometimes called frames and datagrams Packets contain not only data but also the destination IP address Ping Ping Packet Internet Groper is a utility used to find out if a particular IP address is present online an...

Page 58: ...f the TCP IP protocol set is UDP which is used to send data when accuracy and guaranteed packet delivery are not as important for example in realtime video and audio transmission The IP component of TCP IP provides data routability meaning that data packets contain the destination station and network addresses enabling TCP IP messages to be sent to multiple networks within the LAN or in the WAN Te...