46 - DRR245 -
User manual
67
retr.
Retransmission
Retransmission for output 0-10 V or 4..20 mA (Short-circuit pins 9 and 10
to use linear output in Volt). Parameters 68 and 69 define the lower and
upper limits of the scale.
dis.
Disabled
uo. p.
Retransmits process in Volt
ma. p.
Retransmits process in mA
uo. c.
Retransmits command setpoint in Volt
ma. c.
Retransmits command setpoint in mA
uo.o.p.
Volt output percentage
ma.o.p.
mA output percentage
uo.a.1
Volt alarm 1 setpoint
ma.a.1
mA alarm 1 setpoint
uo.a.2
Volt alarm 2 setpoint
ma.a.2
mA alarm 2 setpoint
uo.t.a.
Volt T.A.
ma.t.a.
mA T.A.
68
Lo.L.r.
Lower Limit Retransmission
Output V / mA retransmission lower limit range
-999..+9999 [digit
] (degrees.tenths for temperature sensors),
Default
:
0.
69
up.L.r.
Upper Limit Retransmission
Output V / mA retransmission upper limit range
-999..+9999 [digit
] (degrees.tenths for temperature sensors),
Default
:
1000.
70
bd.rt.
Baud Rate
Select baud rate for serial communication
4.8 k
4.800 Bit/s
9.6 k
9.600 Bit/s
19.2k
19.200 Bit/s (
Default
)
28.8k
28.800 Bit/s
39.4k
39.400 Bit/s
57.6k
57.600 Bit/s