16 - ATR224 - DRR224 - User manual

7.8 

Soft-Start Function

The devices is provided with two types of softstart selectable on parameter 264 

SS.tY.

 (

“Softstart Type”

).

1  First selection (

GrAd.

) enables gradient softstart. AAt starting the controller reaches setpoint basing 

on the rising gradient set on parameter 266 

SS.Gr.

 (

“Softstart Gradient”

) in Unit/hour (ex. °C/h). If 

parameter 269 

SS.ti.

 (

“Softstart Time”

) is different to 0, at starting when the time selected on par. 

269 is elapsed, the controller stops to follow the gradient and reaches setpoint with the maximum 

power.

2  Second selection (

PErc.

) abilita enables output percentage softstart. On par. 268 

SS.tH.

 it is possible to 

set the threshold under which starts the softstart (

“Softstart Threshold”

). On par. 267 

SS.PE.

 (

“Softstart 

Percentage”

) an output percentage is selectable (from 0 to 100), which controller keeps until the 

process exceeds the threshold set on par. 268 or until the time in minutes set on par. 269 

SS.ti.

(

“Softstart Time”

 word 2084).

If the Sof-Start function is active the automatic/manual Tuning function cannot be activated.

 Reading and confi guration through NFC

Programmable

via RFID /NFC.

No wiring required!

Scan the Qr-Code 

to download the App 

on Google Play Store®

The controller ATR224 and DRR224 is supported by the App MyPixsys: using an ANDROID smartphone 

with NFC connection it is possible to program the device without using a dedicated equipment. The 

App allows to read, set and backup all parameters which are stored into the internal memory of Pixsys 

devices.

Procedure:

•  Identify the position of the NFC antenna on the smartphone (usually central, behind the back cover) 

or to one of the sides in case of metal chassis. The antenna is placed on the frontal panel: between 

 and 

FNC

 keys for the ATR224 and between 

 

 keys for the DRR224.

•  Make sure that the NFC sensor of the phone is enabled or that there are no metal materials between 

the phone and the device (ex. aluminium cover or with magnetic stand)

•  It is useful to enable the system sounds on the smartphone, as the notification sound confirms that 

the device has correctly been detected.

The App interface is provided with four tabs: SCAN, DATA, WRITE, EXTRA.

Select the first tab 

“SCAN”

 to read data stored into the internal memory of the device; place the 

smartphone in contact with the controller frontal panel, making sure that the phone’s antenna 

matched with that of the controller. 

Once detected the device, the App emits a notification sounds and proceeds with the model identifi-

cation and the reading of the parameters.

The graphic interface shows the advancement and switches to the second tab 

“DATA”

. It is now possible 

to move the smartphone away from the controller to make the required modifications more easily.

The device parameters are divided into collapsible groups and are displayed with name, current value 

and reference index to the manual. Click on a row to open the setting screen of the related parameter 

with the detailed view of available options (in case of multiple choice parameters) or of the minimum/

maximum/decimals limits (for numeric parameters), included the text description (as per section n. 11 

of the user manual). Once selected the chosen value, the related row will be updated and underlined 

into the tab 

“DATA”

 (hold down the line to cancel modifications).

Summary of Contents for ATR224

Page 1: ...ATR224 DRR224 Controller Regolatore R gulateur User manual Manuale d uso Manuel utilisateur...

Page 2: ......

Page 3: ...ion for output control 15 7 7 LATCH ON Function 15 7 8 Soft Start Function 16 8 Reading and configuration through NFC 16 8 1 Configuration through memory card 17 8 2 Memory card creation update 17 8 3...

Page 4: ...5 7 7 Funzione LATCH ON 45 7 8 Funzione Soft Start 46 8 Lettura e configurazione via NFC 46 8 1 Configurazione tramite memory card 47 8 2 Creazione aggiornamento della memory card 47 8 3 Caricamento c...

Page 5: ...rales 68 3 2 Caract ristiques Hardware 68 3 3 Caract ristiques Software 68 3 4 Mode de programmation 69 4 Dimensions et Installation 69 5 Raccordements lectriques 69 5 1 Plan des connexions 70 5 1 a A...

Page 6: ...ransportation systems Only qualified personnel should be allowed to use device and or service it and only in accordance to technical data listed in this manual Do not dismantle modify repair any inter...

Page 7: ...or noise filter to peripheral devices that generate noise in particular motors transformers solenoids magnetic coils or other equipment that have an inductance component When a noise filter is used at...

Page 8: ...s PT100 PT500 PT1000 Ni100 PTC 1K NTC 10K 3435K Input V mA 0 1 V 0 5 V 0 10 V 0 20 o 4 20 mA 0 60 mV Pot Input 1 150 K Tolerance 25 C 0 2 1 digit on F s for thermo couple thermoresistance and V mA Col...

Page 9: ...raibili 72 mm 90 mm 64 mm Din rail mounting guide EN50022 Attacco a guida DIN EN50022 Memory Card USB optional Cod 2100 30 013 24 23 22 24 230V AC DC PT100 TC NI100 A V PTC NTC DI1 PNP V 21 20 19 1 NO...

Page 10: ...gid copper wire with diameter 0 2 to 2 5 mm min AWG30 max AWG14 Minimum temperature rating of the cable to be connected to the field wiring terminals 70 C Cable stripping lenght 7 to 8 mm Tighten scre...

Page 11: ...so Red Bianco White Rosso Red 13 14 15 ATR224 12ABC For thermoresistances NTC PTC PT500 PT1000 and linear potentiome ters When shielded cable is used it should be grounded at one side only to avoid gr...

Page 12: ...he solid state relay to the pin 0V 12 DO1 PNP 15 0V DRR224 12ABC 0V DO1 PNP 9 10 5 1 e Relay output Q1 Q2 for ATR224 12ABC 3 4 5 Q1 2A230V Resistive 1 8HP Q2 2A230V Resistive 1 8HP 7 8 Capacity 2 A 25...

Page 13: ...ugh serial Flashes when the remote setpoint is enabled 6 2 Keys 11 Increases the main setpoint During configuration allows to scroll the parameters or the groups of parameters Increases the setpoints...

Page 14: ...is operation Tune threshold Setpoint Set Deviation Tune par 74 s d t 1 Ex if the sepoint is 100 0 C and the Par 32 s d t 1is 20 0 C the threshold to calculate PID parameters is 100 0 20 0 80 0 C For a...

Page 15: ...e 7 7 LATCH ON Function For use with input pot and with linear input 0 10 V 0 40 mV 0 4 20 mA it is possible to associate start value of the scale par 4 L L i 1 to the minimum position of the sensor a...

Page 16: ...tion of the NFC antenna on the smartphone usually central behind the back cover or to one of the sides in case of metal chassis The antenna is placed on the frontal panel between and FNC keys for the...

Page 17: ...normally but if its data are considered valid it is possible to view on the display memo skip Press SET in order to start the product without uploading any data from the memory card Configure set the...

Page 18: ...t configuration 10 1 Parameters list functioning The controller integrates many features that make the configuration parameters list very long To make it more functional the parameters list is dynamic...

Page 19: ...2 NTC 10K 3694K 40 C 150 C ntc 3 NTC 2252 3976K 40 C 150 C 2 d P 1 Decimal Point 1 Select number of displayed decimal points for AI1 0 Default 0 0 1 decimal 0 00 2 decimals 0 000 3 decimals 3 deGr Deg...

Page 20: ...FL 1 Conversion Filter AI1 ADC Filter Number of sensor readings to calculate mean that defines process value NB When readings increase control loop speed slows down 1 15 Default 10 12 c Fr 1 Conversi...

Page 21: ...setpoint 1 9999 30000 digit1 p 33 degrees for temperature sensors Default 1750 42 c re 1 Command Reset 1 Type of reset for command contact 1 always automatic in P I D functioning A rEs Automatic Reset...

Page 22: ...atic Manual 1 Enables the automatic manual selection for command 1 diSab Disabled Default Enab Enabled En Sto Enabled with memory 49 ini S Initial State Choose the state of the controller when turning...

Page 23: ...ral disabled Default 0 0 77 d t 1 Derivative Time 1 Derivative time for process 1 P I D regulation Normally of integral time 0 0 1000 0 sec 0 0 derivative disabled Default 0 78 d b 1 Dead Band 1 Dead...

Page 24: ...temp sensors Default 3 0 91 ma p 1 Maximum Proportional Band 1 Selects the max proportional band 1 value selectable by the automatic tune for the P I D regulation of process 1 0 10000 digit1 p 33 degr...

Page 25: ...resis 9999 9999 digit1 p 33 degrees for temp sensors Default 0 5 129 A 1 L L Alarm 1 Lower Limit Lower limit selectable for the alarm 1 setpoint 9999 30000 digit1 p 33 degrees for temp sensors Default...

Page 26: ...Absolute Upper Activation Absolute referred to the process active over Ab Lo a Absolute Lower Activation Absolute referred to the process active under bAnd Band alarm command setpoint alarm setpoint...

Page 27: ...Contact or closed valve If the alarm output is digital SSR off Digital output OFF Default on Digital output ON 151 A 2 Ld Alarm 2 Led Defines the status of the led A2 in correspondence of the relevant...

Page 28: ...M GROUP Q sft s Soft start and mini cycle 264 SS TY Soft Start Type Enables and selects the soft start type diSab Disabled Default Grad Gradient Perc Percentage only with pre programmed cycle disable...

Page 29: ...hich display is switched off when Display Timout expires disp 1 Display 1 disp 2 Display 2 Default dsp 1 2 Display 1 and 2 d 1 2 Ld Display 1 2 and led 282 v out Voltage Output Selects the voltage on...

Page 30: ...active below Hysteresis value greater than 0 Par 128 a 1 HY 0 Time Hysteresis parameter 0 Alarm output OFF OFF ON ON Alarm Spv Pv Absolute alarm active below Hysteresis value lower than 0 Par 128 a 1...

Page 31: ...er than 0 Par 128 a 1 HY 0 Command Spv Time Hysteresis parameter 0 Pv Alarm Spv H Alarm Spv L Alarm output ON OFF OFF OFF ON ON Hysteresis parameter 0 Asymmetric band alarm with hysteresis value lower...

Page 32: ...waiting 13 high limit Selection Messagedisplayedinthealarmevent 14 low limit 15 external alarm 16 temperature alarm 17 pressure alarm 18 fan command 19 cooling 20 operating By setting 0 no message wil...

Page 33: ...hibited if the controller is in alarm mode Activates only if alarm condition reappers after that it was restored 3 Changing the control setpoint the alarm will be disabled It will stay disabled as lon...

Page 34: ...Upper Limit Setpoint 1 21 42 c re 1 Command Reset 1 21 43 c S e 1 Command State Error 1 21 44 c Ld 1 Command Led 1 21 45 c de 1 Command Delay 1 22 46 c S p 1 Command Setpoint Protection 1 22 48 a ma...

Page 35: ...u L Alarm 2 Upper Limit 27 149 a 2 re Alarm 2 Reset 27 150 A 2 S e Alarm 2 State Error 27 151 A 2 Ld Alarm 2 Led 27 152 a 2 de Alarm 2 Delay 27 153 A 2 S p Alarm 2 Setpoint Protection 27 154 A 2 Lb A...

Page 36: ......

Page 37: ...ni di sicurezza e settaggio contenute in questo manuale Avant d utiliser le dispositif lire avec attention les renseignements de s ret et installation contenus dans ce manuel PIXSYS s r l www pixsys n...

Reviews: