Pittway System Sensor SP100ADA Series Installation And Maintenance Instructions Download Page 1

D400-55-00

1

 I56-691-03

SP100ADA Series Dual-transformer

Speaker/Strobes for Fire Protective

Signaling Systems

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

NOTICE:

 This manual should be left with the owner/user

of this equipment.

General Description

The National Fire Protection Association (NFPA) has pub-
lished standards and recommended practices for the speak-
ers described in this manual. As a result, the installer must
be familiar with these requirements as well as all local
codes and special requirements of the authority having ju-
risdiction.

SP100ADA series speaker/strobes can be operated with dis-
tribution amplifiers having an output voltage of either 25
volts or 70.7 volts.

The speakers operate at any one of six input power levels.
The output sound level is selected at the time of installa-
tion, but can be changed, if necessary.

The speaker is also equipped with a capacitive input to al-
low for DC supervision.

The SP100ADA Series Speaker/Strobe is equipped with an
attached 15, 15/75, 75, or 110 candela (cd), UL 1971 listed
strobe. Although they are shipped as a unit, the strobe and
speaker are electrically independent and require separate
power sources. Strobes can be powered by means of a 24V
regulated or full-wave rectified unfiltered supply.

Installation - For Strobe Replacement See NFPA 72,

Chapter 6

All wiring must be installed in compliance with the Na-
tional Electrical Code and all applicable local codes as well
as any special requirements of the authority having juris-
diction, using the proper wire size. This also includes all
applicable NFPA Standards, ANSI/UL 1480, and NEC 760.

Figure 1. Electrical connections:

Specifications

Mechanical

Input Terminals:

12 to 18 AWG (3.31 to 0.82 mm

2

)

Speaker Size:

4 inches (101 mm)

Grille Size:

5" (127 mm) square

Electrical (Speaker)

Voltage Input:

25 volts or 70.7 volts (nominal)

Frequency Range:

400 - 4000 Hz

Operating Temperature Range:

32

°

 to 120

°

F (0

°

 to 49

°

C)

Electrical

1. Connect the speaker/strobe as shown in Figure 1. Keep

in mind that even though the speaker and strobe are a
single mechanical unit, they are electrically independent
and require separate power sources.

NOTE:

Do NOT loop electrical wiring under terminal
screws. Wires connecting the device to the control
panel must be broken at the device terminal con-
nection in order to maintain electrical supervision.

2. Notice that the speaker circuit board is equipped with

two sets of posts and associated electrical jumper wires.
One set of posts is numbered 1 through 6 while the other
is labeled 

A

 and 

B

. Both electrical leads are fitted with a

barrel connector. These two sets of posts and leads en-
able the installer to select any one of six sound pressure
levels with either a 25 volt or 70.7 volt amplifier.

firealarmresources.com

Summary of Contents for System Sensor SP100ADA Series

Page 1: ... wave rectified unfiltered supply Installation For Strobe Replacement See NFPA 72 Chapter 6 All wiring must be installed in compliance with the Na tional Electrical Code and all applicable local codes as well as any special requirements of the authority having juris diction using the proper wire size This also includes all applicable NFPA Standards ANSI UL 1480 and NEC 760 Figure 1 Electrical conn...

Page 2: ...amplifier voltage input power level combina tion being used NEVER connect the yellow jumper to the posts numbered 1 through 6 or the blue jumper to lettered posts A or B Mechanical Slotted head screws are included for attaching the speaker to the electrical junction box Insert the decorative filler plugs supplied into the remaining two holes in the grille Mounting See Figure 2 The speaker can be f...

Page 3: ...0 120 275 290 1 0 Note Inrush current lasts on the order of microseconds Table 3 SP100W24MC LO 1 5 cd UL 1638 Strobe M 15 cd UL 1638 Strobe 24 24 VDC Strobe SP100W Round Grille White Speaker SP101W Square Grille White Speaker SP101R Square Grille Red Speaker C Ceiling mount SP1R2415ADA 15 15 cd UL 1971 Strobe 1575 15 cd UL 1971 Strobe 75 75 cd UL 1971 Strobe 110 110 cd UL 1971 Strobe 24 24 VDC Str...

Page 4: ...are activated System Sensor recommends that the speaker and signal strobe always be used in combination so that the risks from any of the above limitations are minimized WARNING The Limitations of Speaker Strobes Three Year Limited Warranty System Sensor warrants its enclosed speaker strobe to be free from defects in materials and workmanship under normal use and service for a period of three year...