Pittway Notifier SDX-551 Installation And Maintenance Instructions Download Page 1

®

Division of Pittway Corporation

D500-02-00

1

I56-309-03

Notifier, 12 Clintonville Rd., Northford, CT, 06472 (203) 484-7161

INSTALLATION AND MAINTENANCE INSTRUCTIONS

FOR MODEL SDX-551/SDX-551TH PLUG-IN INTELLIGENT

PHOTOELECTRONIC SENSOR WITH COMMUNICATIONS

Before installing sensors, please thoroughly read the system wiring and installation manual, which provides detailed in-
formation on sensor spacing, placement, zoning, and special applications. Copies of these manuals are available from
Notifier.

GENERAL DESCRIPTION

The model SDX-551/SDX-551TH photoelectronic sensor utilizes a state-of-the-art, optical sensing chamber. This sensor
is designed to provide open area protection, and to be used with compatible UL-listed NOTIFIER control panels only.
Suitable for use with panel Model AM2020, Loop Interface Board, LIB-200; compatibility ID:A; maximum number of sen-
sors per loop is 99. See 155-531, Revision A, for installation and wiring diagrams.

Two LEDs on each sensor light to provide a local 360° visibility of the sensor indication. The LEDs can be latched ON by
code command from the panel for an alarm indication. The LEDs can also be unlatched to the normal condition by code
command. Remote LED annunciator capability is available as an optional accessory (part no. RA400Z).

The SDX-551TH adds a thermal heat collector that alarms at a fixed temperature of 135° F.

SPECIFICATIONS

Diameter:

6.1 inches (15.5 cm) installed in BX-501
4.1 inches (10.4 cm) installed in B501

Height:

2.3 inches (5.8 cm)
Add 0.5 inches (1.3 cm) for thermal models

Weight:

9.6 ounces (272 gm)

Installation Temperature Range

SDX-551:

32° to 120° F (0° to 49° C)

SDX-551TH:

32° to 100° F (0° to 38° C)

Operating Humidity Range:

10% to 93% Relative Humidity

Mounting:

BX-501 flanged base
B501 flangeless base
B501 with RMK400 recessed mounting kit

Maximum Air Velocity:

3000 Ft./Min. (15 m/S)

Voltage Range:

15 to 32 Volts DC Peak

Standby Current:

150 

µ

A @ 24 VDC

LED Current:

6 mA @ 24 VDC

WIRING GUIDE

Refer to the installation instructions for the particular plug-in base being used: 1) for the BX-501 base (D550-01-01); 2) for
the B501 base (D550-02-00); 3) for the RMK400 used with the B501 base (D450-07-00). Bases are provided with screw
terminals for power, ground, and remote annunciator connections. See Figure 1.

NOTE: All wiring must conform to applicable local codes, ordinances, and regulations.

NOTE: Verify that all sensor bases are installed and that the wiring polarity is correct at each base.