Pittway NOTIFIER FCM Series Quick Start Manual Download Page 1

DN-6724  —  Page 1 of 4

FCM-1 Module

(See wiring diagram Fig. 5 for FRM-1)

GENERAL

FCM-1 Control Module

 — The FCM-1 Addressable

Control Module provides the NOTIFIER AFC-600 control
panel for a circuit of Notification Appliances (horns, strobes,
speakers, etc.) or to monitor a telephone circuit.
Addressability allows the FCM to be activated, either manu-
ally or through panel programming, on a select (zone or
area of coverage) basis.

FRM-1 Relay Module

 — The FRM-1 Addressable Re-

lay Module provides the AFC-600 with a dry-contact output
for activating a variety of auxiliary devices, such as fans,
dampers, control equipment, etc.  Addressability allows the
dry contact to be activated, either manually or through panel
programming, on a select basis.

FlashScan

 (patent pending) is a new communication

protocol developed by NOTIFIER Engineering that greatly
enhances the speed of communication between analog in-
telligent devices.  Intelligent devices communicate in a
grouped fashion.  If one of the devices within the group
has new information, the panel CPU stops the group poll
and concentrates on single points.  The net effect is re-
sponse speed 

greater than five times that of other de-

signs.

FEATURES

• Built-in type identification automatically identifies these

devices to the control panel.

• Internal circuitry and relay powered directly by two-wire

SLC loop.  The FCM module requires power (for horns,
strobes, etc.), audio (for speakers), or a telephone riser
(for handsets).

• Built-in PS monitor replaces end-of-line relay (FCM only).

• Integral LED “blinks” green each time a communication

is received from the control panel and turns on in steady
red when activated.

• LED blink may be deselected globally (affects all devices).

• High noise immunity (EMF/RFI).

• The FCM may be used to switch 24-volt NAC power, audio

(up to 70.7 V

RMS

) or telephone.

• Wide viewing angle of LED.

• SEMS screws with clamping plates for wiring ease.

• Direct-dial entry of address (01-159).

• Speaker, audible/visual, and telephone applications may

be wired for Class B or A (Style Y or Z).

ISO-9001

Engineering and Manufacturing

Quality System Certified to

International Standard ISO-9001

Made in the U.S.A.

This document is not intended to be used for installation purposes.  We try to keep our
product information up-to-date and accurate.  We cannot cover all specific applications or
anticipate all requirements.  All specifications are subject to change without notice.  For
more information, contact NOTIFIER.   Phone: (203) 484-7161  FAX: (203) 484-7118

One Fire-Lite Place, Northford, Connecticut  06472

FCM and FRM Series

Control and Relay Modules

with FlashScan™

June 18, 1999

H-230

Section:  Intelligent/Addressable Devices

PRELIMINARY

FlashScan™ is a trademark of NOTIFIER.

Noryl® is a registered trademark of GE Plastics, a subsidiary of
General Electric Company.

6724mod2.tif

APPLICATIONS

The FCM is used to switch 24 VDC audible/visual power,
high-level audio (speakers), or control telephone devices.
The FRM may be programmed to operate dry contacts for
door holders, Air Handling Unit shutdown, etc., and to re-
set four-wire smoke detector power.

CONSTRUCTION

• The face plate is made of off-white Noryl®.

• Controls include two rotary switches for direct-dial entry

of address (01-159).

• The FCM is configured for a single Class B (Style Y) or

Class A (Style Z) Notification Appliance Circuit.

• The FRM provides two Form-C dry contacts that switch

together.

OPERATION

Each FCM or FRM uses one of 159 possible module ad-
dresses on a SLC loop.  It responds to regular polls from
the control panel and reports its type and status, including
the open/normal/short status of its Notification Appliance

S3705

Reviews: