2018PC-P03/03
14
MOBILE HOME INSTALLATION
The stove has been tested and listed for mobile home installations.
Unit must be installed in accordance with the:
Manufactured Home
and Safety Standard EN14785:2006,CFR
In addition to all previously detailed requirements, mobile home
installations must observe the following:
- Permanentlyboltthestovetothefloor.Use4 screws[A]throughthe
4 holes placed at left and right side in the base plate as shown in
figure 21.
- Electricallygroundthestovetothemetalchassisofthehomeusinga
number8,gaugeorlargercopperwire[B].
- Maintain an effective vapor barrier at location where PL vent exits the
structure.
- Floor protection and clearances requirement must be followed
precisely as shown in the previous paragraphs.
- PL Vent must be used for exhaust venting. (Single wall vent is not
allowed). Follow PL Vent manufacturer’s installation directions and
observe all listed clearances to combustibles.
- Check any other local buildings codes or other codes that may apply.
WARNING: DO NOT INSTALL IN A SLEEPING ROOM.
Combustion air must come from the outside of the mobile
home!
Failure to do so may create negative pressure within the
mobile home and could disrupt proper venting and operation
of the pelletstove.
The user mustroutinely inspect the point where air is drawn
intoinsurethatitisclearofleaves/debrisandiceorsnow.
CAUTION: THE STRUCTURAL INTEGRITY OF THE FLOORS,
WALLS, CEILING AND ROOF MUST BE MAINTAINED.
The stove is hot while running. Keep children, clothing and
furniture away. Contact may cause skin burns.
Keep combustible materials such as grass, leaves, etc. at
least 4ft awayfromthe point directly under the vent
termination.
Fig.21