Hunter-Pro Series Captain 8 - Installation Guide
60
7
Key #4: Timers, Counters
See the menu screens, starting page 93.
7.1.
Entry/Exit delays
Set the entry delay 1 and 2 and the exit delay, in seconds (max. 250). Press [NEXT] to set the
next delay. To use entry delay 2 per zone, see parameter “T” on page 47.
7.2.
Output type timers
Set the timers of the output types that trigger the physical outputs. These timers set the output’s
trip time. The timers operating options are listed in the next table see section 10.2, on page 65 for
more details on output types.
Time
The output type is activated...
0
For as long as the panel is armed
1-9998 (sec.) For this time span
9999
For as long as the event that had triggered it has not been restored. For
example, the phone (line) fault output type can trigger a relay, which
will be tripped for as long as the line is faulty.
The following table lists the output types that have timers and their default times.
Output type
Time (sec.)
Output type
Time (sec.)
Ext. Siren triggered
240
Mains Fault
9999
Int. Siren triggered
240
Low Battery
9999
Burglary alarm
240
Phone Failure
9999
Anti Mask alarm
240
Zone Tamper
9999
Special Burglary 1 alarm
240
Zone Bypass
9999
Special Burglary 2 alarm
240
GSM Fault
9999
Smoke alarm
240
Communication Fault
9999
Fire alarm
240
Tag Activation
240
Special Fire alarm
240
Door code entered
5
Panic alarm
240
Wireless Remote
5
Silent Panic alarm
240
Test executed
5
Hold Up alarm
240
Audio Device triggered
60
Medical alarm
240
Remote control*
60
Tamper alarm
240
Zone Open Hold T**
0 (min.)
* This output type is triggered when a physical output is activated by telephone.
** This output type is triggered when the alarm system is disarmed and the last open zone is
closed. When countdown expires, the assigned physical output can be used for energy saving
- turning off the lights, for example.
7.3.
AC report delay
Set a time (in minutes, max. 250) to delay AC fault reports. The default is 15 min.