Operation
Operating Manual PSSu E F 4DO 0.5(-T)(-R)
21316-EN-08
30
7
Operation
7.1
Messages
A module error is displayed via the "Err" LED (see section entitled "Display elements"). It is
signalled to the head module and then entered in the
}
Error stack, with PSSu in system environment A
}
Diagnostic log, with PSSu in system environment B.
of the head module.
The module can detect the following errors:
Module error
Statement
Remedy
Start-up error
Error as the PSSu system starts
up
Change faulty module.
Configuration error
Incorrect module type configured.
The configured hardware registry
does not match the actual hard-
ware registry.
FS communication error
Error during FS communication
Change faulty module.
Bus termination error
There is no terminating plate or
there is a bad contact with the
module bus.
Install a terminating plate with in-
tegrated end bracket or insert the
base modules together correctly.
Temperature error: too warm (
1
)
Ambient temperature too high:
Error stack entry/diagnostic log
entry
Ensure there is sufficient ventila-
tion in the control cabinet or pre-
vent overload.
Temperature error: too hot (
1
)
Ambient temperature too high:
Reset the module and stop the af-
fected I/O-Groups (SafetyBUS p)
Ensure there is sufficient ventila-
tion in the control cabinet or pre-
vent overload.
Output error
Error during cyclical output test for
short circuit. Possible causes:
Short circuit, or output defective.
Rectify the short circuit or change
the faulty module.
Error in the (local) enable principle FS output has reacted incorrectly
or unexpectedly
Check configuration.
(
1
) There are two levels of overtemperature.
}
Too warm:
If a module's temperature exceeds a threshold value, the module sends a warning to
the head module. If the temperature drops back below the threshold value, the module
sends an all-clear.
}
Too hot:
If a module's temperature exceeds a further threshold value, the module sends an error
message to the head module and triggers an I/O-Group stop.