PSSnet SLL
Pilz GmbH & Co. KG, Felix- Wankel- Straße 2, 73760 Ostfildern, Germany
13
2.1.2
Installing the SFP modules (if present)
Figure 2: 1 - Fast EHTERNET fiber optic SFP module
2 - Gigabit ETHERNET fiber optic SFP module
To attach an SFP module, first remove the protective cap over the socket.
Push the SFP module with the lock closed into the socket until it latches
audibly in place.
Note:
Only use Pilz SFP modules.
2.1.3
Connecting the terminal block for the supply voltage
and the grounding
A 3-pin terminal block is used for the grounding and for connecting the supply
voltage.
Warning!
Only connect a supply voltage that corresponds to the type plate of
your device.
Note:
Relevant for North America:
The tightening torque of the terminal screws is max. 4.4 lb in. (0.5 Nm).
Pull the terminal block off the device.
Connect the supply voltage lines.
Connect the ground connection.
2.1.4
Mounting the device on the DIN rail
Caution!
Do not open the housing.
Figure
Pin
Assignment
Voltage range
1
+ 24 V
9.6 to 32.0 V DC
2
0 V
3
Ground connection
Table 2: Pin assignment of the 3-pin terminal block for the supply voltage
1
2
1
2
3
+24 V
0 V