Automatic restart
The OSSDs automatically switch to the ON state during operation under the following con-
ditions:
}
both OSSDs are wired correctly
and
}
no error has occurred
and
}
the protected field is clear
and
}
at least 80 ms have elapsed since the switch to the OFF state.
[1]
[2]
[3] [4]
[5]
POWER
OSSD
2
3
4
[6]
t
1
t
t
t
Protected
field
Free
Interrupted
ON
OFF
ON
OFF
Fig.: Automatic start and restart timing diagram
Legende
[1]
Safety light grid is switched on
[2]
Check completed successfully, OSSDs in the ON state
[3]
Protected field broken
[4]
OSSDs in the OFF state
[5]
Protected field is clear again, check for errors is restarted
[6]
OSSDs in the ON state
t
1
Check is begun to determine whether the protected field is clear and whether
there are errors
t
2
Response time required for the OSSDs to switch to the OFF state (see
)
t
3
Minimum time that the OSSDs remain in the OFF state: 80 ms