PSEN cs6.2p
Operating Manual PSEN cs6.2p
1003430-EN-06
| 11
The results of the sensor diagnostics can be checked already during the installation phase
via the display in the fieldbus module, without the need to connect the fieldbus module to
the network.
}
With Safety Device Diagnostics there are the following diagnostic options for the fieldbus
module for simple wiring:
– Information is passed on via the fieldbus module directly to the network
– Mappings of the signal outputs to the sensor are automated by the SDD.
This prevents wiring errors and an expansion or reduction of the sensors is possible
without the need to change existing wiring.
– Wiring in accordance with IP20: Rapid installation in the control cabined is enabled.
– Wiring in accordance with IP67: Various passive junctions can be used (see
) to connect several sensors with only one cable
from the field in the control cabinet.
Further information on Safety Device Diagnostics can be found in
Operating distances
Actuator PSEN cs6.1
Actuator PSEN cs6.1
low profile glue or
PSEN cs6.1 low pro-
file screw
[1]
DEVICE
INPUT
SAFETY GATE
[4]
[1] Actuator PSEN cs6.1 aligned to the square marking on
the switch
S
ao
Assured operating distance: 8 mm
S
ar
Assured release distance: 20 mm
S
o
Typical operating distance: 11 mm
S
r
Typical release distance: 14 mm
[4] Actuator PSEN cs6.1 low profile glue or PSEN cs6.1 low
profile screw aligned to the square marking on the switch
S
ao
Assured operating distance: 5 mm
S
ar
Assured release distance: 20 mm
S
o
Typical operating distance: 10 mm
S
r
Typical release distance: 12 mm