Fieldbus Modules
Operating Manual Communication interfaces
1002971EN03
27
Description
Input data from PNOZmulti 2
Virtual inputs i0 – i31
4 Input Bytes
Virtual inputs i32 – i63
4 Input Bytes
Virtual inputs i64 – i95
4 Input Bytes
Virtual inputs i96 – i127
4 Input Bytes
Output data
The Master reads the virtual outputs of the PNOZmulti 2.
Description
Output data from PNOZmulti 2
Virtual outputs o0 – o31
4 Output Bytes
Virtual outputs o32 – o63
4 Output Bytes
Virtual outputs o64 – o95
4 Output Bytes
Virtual outputs o96 – o127
4 Output Bytes
4.6.2
Access to table segments
The data in the tables (see
) can be requested via the following mod
ules.
Input data
The Master requests a table segment in the form:
Description
Input data from PNOZmulti 2
Table and segment number
2 Input Bytes
Output data
The PNOZmulti 2 replies in the form:
Description
Output data from PNOZmulti 2
Table and segment 13 Byte payload
15 Output Bytes
A detailed description is available in the chapter entitled
4.6.3
LED status
The LED status of the PNOZmulti 2 can be requested directly via the following module.
Description
Output data from PNOZmulti 2
LED status
1 Output Byte
}
Bit 0 = 1: LED OFAULT is lit or flashes
}
Bit 1 = 1: LED IFAULT is lit or flashes
}
Bit 2 = 1: LED FAULT is lit or flashes
}
Bit 3 = 1: LED DIAG is lit or flashes
}
Bit 4 = 1: LED RUN is lit