Switch functions
The following switch functions can be configured:
}
Standstill
The standstill frequency is configured centrally. The standstill frequency should be the
lowest frequency in the configuration.
All switch function parameters are pre-configured to the lowest frequency ex works.
}
Speed
Limit values can be configured to monitor for overspeed.
Limit values should be entered in ascending order (Parameter set P0 -> lowest values,
parameter set P15 -> highest values)
}
Speed range
Up to 4 speed ranges can be monitored simultaneously.
Configure two switch functions to monitor a range:
–
F2 and F3,
–
F4 and F5,
–
F6 and F7 or
–
F8 and F9.
The switch function with the lower number (e.g. F2) operates as the lower range limit;
the switch function with the higher number (e.g. F3) operates as the upper range limit.
Both switch functions can be assigned to one or more outputs.
}
Position
Up to 4 different position windows can be monitored: Position 1 ... Position 4.
Each position to be monitored can be entered as often as necessary in parameter sets
P0 to P15 and switch functions F1 to F9.
}
Direction
The monitoring functions "Direct. Left" and "Direct. Right" can be configured as a switch
function as often as necessary.
For both directions, a tolerance can be entered for the wrong direction.