PSEN cs6.11n
Operating Manual PSEN cs6.11n
1004127-EN-03
19
6. Align the safety switch and tighten the screws.
7. Align the actuator and tighten the screws.
Use in operating heights higher than 2000 m above sea level
When using the PSEN cs6.11n note the reduced max. ambient temperature of +60 °C at a
height of 2000 m to 4000 m.
Adjustment
}
The stated operating distances (see
) only apply when the
safety switch and actuator are installed facing each other in parallel. Operating dis-
tances may deviate if other arrangements are used.
}
Note the maximum permitted lateral and vertical offset (see
and
Operation
NOTICE
The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.
Status indicators:
Legend:
LED off
LED on
LED flashes (500 ms on, 500 ms off)
LED flashes quickly (50 ms on, 950 ms off)
LED flashes very quickly (30 ms on, 470 ms off)