49
details, see chapter 5.5.2
Chapter 10 SOC remaining capacity
10.1 SOC Remaining capacity calculating Description
Gate supports the SOC calculation of a single cell, calculated once per minute. The SOC
value within one minute of the first start is invalid and the SOC value in the first minute after
the parameter is reconfigured is invalid.
Battery SOC calculation, without modification in the case, the use of the default battery
characteristics parameters:
Battery voltage rating
2V
12V
Float charge range
-1A to +1A
-1A to +1A
Cut-off voltage
1.75V
10.8V
Recovery voltage
2.12V
12.68V
The default battery parameters can be configured by "Setting"→"Project settings"→"Battery
information"
Battery [recovery voltage] in actual use, after a complete charge and discharge process, you
can update by calculation
(
Take the average value of the recovery voltage of all the batteries
in each group, general requirements to remove the maximum and minimum
),
modify the
configuration parameters for use
,
the battery SOC will be closer to the actual battery
characteristics. It has not been a complete charging and discharging process the SOC is
obtained with current battery status parameters calculated default
,
the error will be greater
than after a complete charge and discharge.
Note:
When the configuration software to replace the battery voltage level
(
Such as 2V change to