T H E M O D E R M - B U S T E C H N O L O Y
60
Ve
rs
io
n E
.3
.0
1.0
0
59
1
02
DIF size, 16 bits integer
60
1
66
VIF External temperature (°C*0,1)
61-62
2
xxxx
Temperature
Object 10, Status for the four Master outputs
63
1
01
DIF size, 8 bits integer
64
1
FD
VIF extension VIF code
65
1
1A
VIFE Digital output (binary)
66
1
xx
0000xxxx
67
1
xx
CS checksum
68
1
16
End character
9.4.3
Write to the relay output
Table 9-5
9.4.4
Writing passed
Table 9-6
Byte No
Size (byte)
Value (Hex)
Description
1
1
E5
Transmission passed
Byte No
Size (byte)
Value (Hex)
Description
1
1
68
Start character
2
1
07
L- field
3
1
07
L- field
4
1
68
Start character
5
1
53/73
C- field , SND_UD
6
1
xx
A- field , address ( Default 251, Hex FB)
7
1
51
CI- field , send data, LSB first
8
1
01
DIF size, 8 bits integer
9
1
FF
VIF next byte is manufacturer specific
10
1
07
VIFE digital output (binary)
11
1
0x
Value to write 01 = relay ON. 00 = relay OFF
12
1
xx
CS checksum, calculated from C field to last data
13
1
16
End character