26
CEO: Dr. Bernt Götz • Phone +493641/66880 • Fax +493641/668866 • www.piezosystem.com
8.10 Data recorder
The data recorder consists of two memory banks that are written to in parallel. In this way, two individual
signals can be stored synchronously.
Example:
A jump via the set command is used to trigger the data recorder and measure the piezo position and
the current of amplifier 1 for 25 ms.
Command list
Result
cl,1
modsrc,0
set,0
<pause to finish step>
recsrc,0,0
recsrc,1,6
reclen,500
recast,1
recstr,1
set,100
<pause to finish step>
recoutf,0
recoutf,1
<plot results>
8.11 Trigger
8.11.1 Trigger In
Various controller functions can be carried out with the trigger input. This can be used to synchronize
the controller with several other
NV200/D NET
controllers or any other external device.
The trigger input uses a 5V logic and is activated by rising edges.
tgrfkt
Action on trigger pulse
0
No action
1
Start the arbitrary waveform generator (equal to
grun,1
), then it switches to synchronization (trgfkt,
3)
2
Increment the arbitrary waveform generator index
3
Set the arbitrary waveform generator index to the start value (
goarb+gsarb
)
4
Synchronize the ILC counter/ Set the internal counter to the beginning of the setpoint curve
5
Start the data recorder (equal to
recrun,1
)