MT334-I
Rev. 0.3 08/04/2022
13 - 22
Document classified as: 2 - Company Confidential
PSW3
Piezoresistive Pressure Sensor 3
–
input power
–
negative
M3
GND
Ground
GND
Ground
DI1
Digital Input 1
DI2
Digital Input 2
DI3
Digital Input 3
DI4
Digital Input 4
DI5
Digital Input 5
DI6
Digital Input 6
DI7
Digital Input 7
DI8
Digital Input 8
DI9
Digital Input 9
DI10
Digital Input 10
M4
GND
Ground
V CPU
CPU Power Supply
V MDM
GSM Modem Power Supply
485 +
RS485 LINE+
485 -
RS485 LINE-
M3
DO1+
Digital Output 1 - positive
DO1-
Digital Output 1
–
negative
DO2+
Digital Output 2 - positive
DO2-
Digital Output 2 - negative
DO3+
Digital Output 3 - positive
DO3-
Digital Output 3 - negative
DO4+
Digital Output 4 - positive
DO4-
Digital Output 4 - negative
Table 3: Description of the available clamps
6.2
Prescaler
Clamps DI9 and DI10 (M3-11, M3-12) have two independent prescalers that can be enabled via selector
LK3 and LK2 respectively.
In this mode the frequency of the input pulses is divided by a configurable factor from 8 to 4096, this
allows to extend the range of input pulse frequencies up to 12KHz.
The prescalers are configured by the LK4 and LK5 selectors; the available options are shown in Tables 4
and 5.
Figure 6: Selectors for enabling and configuring the prescalers for digital inputs DI9 and DI10
LK3
LK5 Prescaler
Frequency
Max
LK2
LK4
Prescaler
Frequency
Max
A-B
-
-
3 Hz
A-B
-
-
3 Hz
B-C
A
1
3 Hz
B-C
A
1
3 Hz
B
8
24 Hz
B
8
24 Hz
C
64
192 Hz
C
64
192 Hz
D
512
1.5 KHz
D
512
1.5 KHz
E
4096
5 KHz
E
4096
5 KHz
Table 4 - DI9 Configuration
Table 5 - DI10 Configuration