61
HBC 975
Use, maintenance and warning manual
SLAM-SHUT VALVE
|
COMMISSIONING
|
REV. 00
EN
8.3 - PROPER COMMISSIONING CHECK
Seal
Procedure
External
Element under pressure
Apply a foaming agent and verify that no internal leaks are
visible.
Internal
Element separating two pressure
chambers
The pressure in the closed chamber with the lower pressure
remains stable for a period of not less than 15 minutes
8.4 - CALIBRATION OF ANY ACCESSORIES
The slam-shut valve is normally supplied already set with the required calibration value, but for safety it is advisable to
check the calibration according to the procedures illustrated in the following chapters.