MAINTENANCE
4-16
/ Husky 12 Foam System
© 2017 Pierce Manufacturing Inc. All Rights Reserved.
4-7.4
Calibrate Class B Foam Mode
MODE SELECT
→
SETUP SELECTION
→
CALIBRATE
→
CLASS A CALIBRATION
NOTE:
•
Prior to calibrating, run the system at different rates and verify that it is in need of calibration.
•
The most accurate calibration can be obtained using the actual foam concentrate intended for
use at a fire incident. However, if foam is unable to be used, water is an acceptable substitute.
•
Verify that the draft hose is securely installed, the Foam Inlet Valve is OPEN, the Foam Pump
is primed, and the foam source is set to DRAFT CLASS B before beginning foam calibration.
Figure
4-25:
Calibrations
Screen
Activation
1557E, 1568B, 1574C
1.
From the normal operation screen (Foam Pump Not Running), navigate to the CALIBRATIONS screen.
2.
In the CALIBRATIONS screen, use the UP/DOWN buttons to highlight Class B Calibration and press ENTER to
bring up the CLASS B CALIBRATION screen.
Figure
4-26:
Class B Calibration Screen
1577B
3.
Display should read CALIBRATE FOAM B 1.00 GPM.
4.
Press ENTER to begin foam calibration at 1.00 GPM. The foam pump will run for five minutes.
5.
Measure actual flow by measuring the foam/water pick-up through draft hose.
6.
When green Foam Pump ON light turns off, measure the actual amount of foam concentrate flowed. Calculate
the gallons per minute (GPM) used during the five minutes.
(Example: 5.5 gallons flowed divided by 5 minutes
= 1.1 GPM.)
Using the ARROW UP or ARROW DOWN buttons, enter the GPM flowed.
(In this example “1.1”)
7.
Press ENTER to accept value.
8.
Display should read: CALIBRATE FOAM B 4.00 GPM
9.
Press ENTER to begin foam calibration at 4.00 GPM. Foam pump will run for five minutes.
10. Measure actual flow by measuring the foam/water pick-up through draft hose
11. When green “Foam Pump On” light turns off, measure the actual amount of foam concentrate flowed. Calculate
the gallons per minute (GPM) used during the five minutes.
(Example: 5.5 gallons flowed divided by 5 minutes
= 1.1 GPM.)
Using the ARROW UP or ARROW DOWN buttons, enter the GPM flowed.
12. Press ENTER to accept value.
13. Display should read CALIBRATE MODE CLASS B FOAM.
HOLD ENTER AND
PRESS ARROWS
PRESS
PAGE
HOLD 5
SECONDS
SCROLL TO
SETUP
SCROLL TO
SETUP