6.5.2 Diagnosis
The module monitoring is always active. A detected error only triggers a diagnostic alarm if
the diagnostic type is activated in the diagnostic check boxes.
Diagnosis type
TM StepDrive module error
Standard
option
Diagnosis
message
missing supply
voltage L+
missing motor voltage
deactivated 17
positioning error
Faulty positioning of the module
(e.g. during positioning, the travel range
was exceeded).
deactivated 740
Power stage error
Error in the power stage (e.g. power stage
driver is not accessible due to a defect).
deactivated 741
DIS input active
A running traversing job was cancelled be-
cause the DIS input of the module was acti-
vated.
deactivated 743
When a diagnostic alarm is triggered by a TM StepDrive error event, the following hap-
pens:
The DIAG light flashes red when a diagnostic alarm is present. The light is switched
off after error correction.
The diagnosis is displayed as plain text in the online and diagnostic view of STEP 7
(TIA Portal
®
).
options for the reaction of a CPU executing your control program