Caution
: Removing a sensor for less than 60 seconds does not produce a trouble alarm.
Removing or unplugging a sensor for more than 60 seconds or plugging in a different
sensor at any time will cause a trouble alarm.
Host and Node Firmware Requirements
The 4-20mA Bridge requires the following firmware versions in the Host and Node(s) for sensor
compatibility:
IMS-4000 Host
• Input board firmware chip version xx.xx.xx.103 or higher
NOTE
: Input board firmware is NOT flash upgradeable. A new firmware chip must be
installed. For information on obtaining a new firmware chip, please contact Sensaphone
Technical Support at 610.558.2700 or via e-mail at
.
• ConsoleView version 2.04 or higher
• IMS4K OS version 2.41 or higher
• Voice version 2.09 or higher
*Host version information is viewable through the ConsoleView software on the
Version Info
screen and the
Help>About
selection from the main menu.
IMS-4000 Node
• Firmware version 2.19 or higher.
*Node version information is viewable through the ConsoleView software on the
Node
Properties>Diagnostics
screen.
Sensor Template
(factory default)
Input Name: Transducer
Recognition Time: 3 Seconds
Reset Time: 0 Seconds
Data Logging: Active
Voice: None
Input Class: Other
Specifications
Input: 4–20mA DC
Current Limit: 50mA
Input Impedance: Variable (1000
Ω
@ 4mA, 260
Ω
@ 20mA)
Accuracy:
±
0.25%
IMS Connection: RJ-45
Operating Temperature Range: 32–122 deg F (0–50 degC)
Housing: Black plastic with mounting ears
IMS-4000 Manual
136
Summary of Contents for Sensaphone IMS-4000
Page 1: ...IMS 4000 User s Manual Version 2 4 8 PHONETICS INC SENSAPHONE ...
Page 44: ......
Page 59: ......
Page 60: ......
Page 102: ......
Page 106: ...IMS 4000 Manual 106 ...
Page 135: ...Chapter 7 IMS 4000 Sensors 135 ...
Page 146: ...IMS 4000 Manual 146 ...
Page 148: ...IMS 4000 Manual 148 ...
Page 158: ...IMS 4000 Manual 158 ...
Page 159: ...159 ...