Ancillary Product Specifications
Phoenix Recommended Cables
33
MKT-0262 MPC-1748 Rev 02/13
APM2 Rough-In Installation Guide
4.5 Phoenix Recommended Cables
Cable
Type
Plenum
Rated
Function
Wire
Gauge
Primary
Vendor/Part #
Alternate
Vendor/Part #
Color Code
Notes
2C
Round
No
24 Vac power to
LOSEA or
Pneumatic (110’
max at load
1, 2
)
18
Belden 9409
1: Red
2: Black
Must be
stranded
24 Vac power to
HiSea (288’ max
at load
1, 2
)
14
Belden 9411
2C
Round
Yes
24 Vac power to
LOSEA or
Pneumatic (110’
max at load
1,
2
)
18
Belden 82740
Windy City
NP002360
1: Red
2: Black
Must be
stranded
24 Vac power to
HiSea (288’ max
at load
1, 2
)
14
Windy City
NP007960
TP
No
FTT-10 (4500’)
TP1250 (425’)
22
Windy City
107500
Connect-Air
W221P-1002
1: White/Blue stripe
2: Blue/White stripe
For more
alternatives
visit:
echalon.com
FTT-10 (8800’)
16
Windy City
109600
TP
Yes
FTT-10 (4500’)
TP1250 (425’)
22
Windy City
105500
Connect-Air
W221P-2001
1: White/Blue stripe
2: Blue/White stripe
For more
alternatives
visit:
echalon.com
FTT-10 (8800’)
16
Windy City
109500
TSP
No
I/O signal
wiring
1
22
Belden 9501
1: Black&Red
Twisted
Shielded Pair
2 TSP
No
I/O signal
wiring
2
22
Belden 9502
1: Black&Red
2: Black&White
Two Twisted
Pair,
Shielded
3C
Round
No
Signal
22
Belden 8443
1: Red
2: Black
3: Green
Must be
stranded
3C or
4C
Round
Yes
Signal
22
Belden 88444
Windy City
004380
1: Red
2: Black
3: Green
4: White (not used as
3C)
Must be
stranded
4C
Round
No
Signal
22
Belden 8444
Manhattan
M13304
1: White
2: Green
3: Black
4: Red
Must be
stranded
5C
Round
No
Signal
22
Belden 8445
Manhattan
M13305
1: White
2: Brown
3: Black
4: Red
5: Green
Must be
stranded