Description of the RFC 4072S
108580_en_02
PHOENIX CONTACT
2.12
Mode selector switch
The mode selector switch is used to define the operating state of the standard controller.
The mode selector switch does not influence the operating state of the safety-related
PROFINET controller (SPNS).
The RUN/PROG and STP (STOP) positions have a toggle button function, and the MRESET
position has a pushbutton function. After the switch has been released in the MRESET posi-
tion, it returns to the STOP position.
Figure 2-29
Mode selector switch
Table 2-10
Operating modes of the RFC
Operating
mode
Explanation
RUN/PROG
The application program is in the “Run” state.
The PLCnext Engineer software can be used for program and configu-
ration modifications.
The monitoring and online functions can be used.
STOP
The application program of the standard controller is in the “Stop” state.
MRESET
Retain data and the application program is deleted.
Press the mode selector switch as follows to delete the retain data and
the application program:
•
Hold the switch in the MRESET position for three seconds.
•
Release the switch for less than three seconds.
•
Hold the switch in the MRESET position for three seconds.
WARNING: PROFIsafe process data exchange inter-
rupted
If the operating mode switch is in the STOP position, process
data between F-Host and F-Devices is not exchanged in the
network via PROFIsafe. The F-Devices assume the safe
state (failure state) after the defined watchdog time has
expired.
107586A009
RUN/PROG
STP
MRESET
Summary of Contents for RFC 4072S
Page 22: ...RFC 4072S 22 272 PHOENIX CONTACT 108580_en_02...
Page 68: ...RFC 4072S 68 272 PHOENIX CONTACT 108580_en_02...
Page 82: ...RFC 4072S 82 272 PHOENIX CONTACT 108580_en_02...
Page 142: ...RFC 4072S 142 272 PHOENIX CONTACT 108580_en_02...
Page 154: ...RFC 4072S 154 272 PHOENIX CONTACT 108580_en_02...
Page 222: ...RFC 4072S 222 272 PHOENIX CONTACT 108580_en_02...
Page 234: ...RFC 4072S 234 272 PHOENIX CONTACT 108580_en_02...
Page 254: ...RFC 4072S 254 272 PHOENIX CONTACT 108580_en_02...
Page 264: ...RFC 4072S 264 272 PHOENIX CONTACT 108580_en_02...
Page 268: ...RFC 4072S 268 272 PHOENIX CONTACT 108580_en_02...
Page 271: ......