B Appendix: terms for PROFIsafe
Terms that are used in connection with PROFIsafe in this user manual are described below.
A definition of PROFIsafe terms is also provided in the PROFIsafe profile.
CRC
Cyclic Redundancy Check
A cyclic redundancy check is used to verify the validity of the process data contained in the
safety telegram, check whether the assigned address relationships are correct, and verify
the safety-related parameters. This value is part of the safety telegram.
Consecutive number
Consecutive number
Method for ensuring that the safe data is transmitted completely and in the correct order.
Reintegration
Removal of passivation for the reintegration of previously passivated F-Devices (see also
F-Parameters
(According to PROFIsafe System Description, version of April 2016)
F-Parameters contain information for adapting the PROFIsafe layer to specific customer
specifications and for checking the parameterization by means of a separate method
(diverse). The main F-Parameters are:
F_Source_Address /
F_Destination_Address /
F_Source_Add /
F_Dest_Add (F-address
for short)
Unique address for F-Devices within a PROFIsafe island. The
technology part of the F-Device compares the value with the
local address switch or with an assigned F-Address in order
to check authenticity of the connection.
As of PROFIsafe profile V2.6.1, a distinction is made between
two address types, which must be specified by the manufac-
turer in the F-Device-specific user documentation:
Address type
1:
The F-Device only checks the F_Destina-
tion_Address.
Address type
2:
The F-Device checks the F_Destination_Ad-
dress and the F_Source_Address.
F_WD_Time
Specifies the time for the watchdog timer in milliseconds. The
timer monitors the time that elapses until the next valid
PROFIsafe message is received.
F_SIL
Indicates the SIL that the user can expect from the relevant F-
Device. It is compared with the manufacturer’s specification
that is stored locally.
F_iPar_CRC
Checksum that is calculated from all iParameters of the tech-
nology-specific part of the F-Device.
F_Par_CRC
CRC signature that is created across all F-Parameters and
ensures error-free transmission of the F-Parameters.
Summary of Contents for RFC 4072S
Page 22: ...RFC 4072S 22 272 PHOENIX CONTACT 108580_en_02...
Page 68: ...RFC 4072S 68 272 PHOENIX CONTACT 108580_en_02...
Page 82: ...RFC 4072S 82 272 PHOENIX CONTACT 108580_en_02...
Page 142: ...RFC 4072S 142 272 PHOENIX CONTACT 108580_en_02...
Page 154: ...RFC 4072S 154 272 PHOENIX CONTACT 108580_en_02...
Page 222: ...RFC 4072S 222 272 PHOENIX CONTACT 108580_en_02...
Page 234: ...RFC 4072S 234 272 PHOENIX CONTACT 108580_en_02...
Page 254: ...RFC 4072S 254 272 PHOENIX CONTACT 108580_en_02...
Page 264: ...RFC 4072S 264 272 PHOENIX CONTACT 108580_en_02...
Page 268: ...RFC 4072S 268 272 PHOENIX CONTACT 108580_en_02...
Page 271: ......