RFC 4072S
PHOENIX CONTACT
108580_en_02
Key:
A
RFC 4072S is reset to the default settings
B
iSPNS 3000 with error code 8008
hex
(diagnostic parameter register (Diag param reg.):
boot project missing)
After successful reset to the default settings, the RFC 4072S reboots and then shows error
code 8008
hex
on the display (see
).
Resetting to the default settings has the following effects:
–
All settings were reset to the default settings.
–
Project and boot project were deleted.
–
All the firmware changes resulting from firmware updates that have been executed until
the time of reset are retained.
–
Settings of the device-internal realtime clock are retained.
In order to start up the RFC 4072S again, proceed as described in
.
7.2
Changing IP address settings via the display
You can also set the IP addresses directly on the device via the display.
•
Open the “CONFIG DETAILS” menu.
•
Select “LAN SETTINGS”, then the “LAN2 SETTING” menu item.
The procedure for assigning the IP address settings is essentially the same for the LAN1,
LAN2 and LAN3.1/3.2 interfaces. Interface LAN2 is described in this example.
You can view and change the IP address defined in the RFC 4072S via the display at any
time, even during operation.
The change to the IP address will only take effect after the RFC has been restarted (e.g.,
via the CONFIG DETAILS menu on the display). The changed IP address is permanently
stored in the parameterization memory. The RFC can then be reached in the network
under the changed IP address.
Assuming the new IP address is in the same subnet as before, the application program
will continue to run without errors after the RFC restart.
Summary of Contents for RFC 4072S
Page 22: ...RFC 4072S 22 272 PHOENIX CONTACT 108580_en_02...
Page 68: ...RFC 4072S 68 272 PHOENIX CONTACT 108580_en_02...
Page 82: ...RFC 4072S 82 272 PHOENIX CONTACT 108580_en_02...
Page 142: ...RFC 4072S 142 272 PHOENIX CONTACT 108580_en_02...
Page 154: ...RFC 4072S 154 272 PHOENIX CONTACT 108580_en_02...
Page 222: ...RFC 4072S 222 272 PHOENIX CONTACT 108580_en_02...
Page 234: ...RFC 4072S 234 272 PHOENIX CONTACT 108580_en_02...
Page 254: ...RFC 4072S 254 272 PHOENIX CONTACT 108580_en_02...
Page 264: ...RFC 4072S 264 272 PHOENIX CONTACT 108580_en_02...
Page 268: ...RFC 4072S 268 272 PHOENIX CONTACT 108580_en_02...
Page 271: ......