PHOENIX CONTACT
3827_en_B
8.1
Configuration via PSI-CONF software
1.
Start the PSI-CONF software (see Section 5.6, “Configuration via PSI-CONF
2.
Create a new network project.
3.
Follow the software wizard.
Figure 8-2
PSI-CONF software: Wizard, Step 3
4.
Select “PLC/Modbus RTU dual mode” and assign a Modbus address.
5.
Follow the software wizard.
In order to enable the master wireless module to communicate with a controller via the
RS-232 or RS-485 interface, you must set the interface parameters. Please note that the
controller settings must match the settings of the wireless module.
Table 8-1
Configuration via PSI-CONF software
The Modbus connection between the controller and the wireless module can be monitored
via a watchdog. For additional information on the watchdog, refer to page 95.
The Modbus address is a unique address in the Modbus network. Assign an address
between 1 ... 247.
Parameter
Possible values
Default setting
Interface type
RS-232, RS-485
RS-232
Data rate
300 ... 115,200 bps
19,200 bps
Parity
None, even, odd
None
Number of stop bits
1; 2
1
Number of data bits
8
8
Modbus address
1 ... 247
1