Configuration and startup
3827_en_B
PHOENIX CONTACT
5.6.3
Device settings
Assign a device name or set the transmission power under “Device Settings”. All device
parameters are listed on the “Overview” tab.
Figure 5-9
PSI-CONF software: Individual Settings, Overview
Depending on the operating mode, configure the serial interface under “Individual Settings”
on the “Serial Port” tab.
In I/O data mode (default upon delivery), both interfaces are deactivated. To activate the
serial interface, select the “Serial data,” “PLC/Modbus RTU mode,” or “PLC/Modbus RTU
dual mode” network application under “Network Settings”.
In order to be able to cover the largest possible distances, the preamplifier has been
activated and transmission power set to 30 dBm by default. When operating the devices
directly next to one another, the receiver might become overloaded. In this case, remove
the antennas, increase the distance between the devices and antennas, or reduce
transmission power using the PSI-CONF software.
Only use one interface per wireless module. Parallel operation of both interfaces is not
possible.