RAD-900-...
PHOENIX CONTACT
3827_en_B
9.6
Error codes and formats for analog input and
output values
The measured value is represented in bits 0 ... 15. Values higher than 8000
hex
indicate an
error.
Analog RAD-AI4-IFS inputs
Table 9-6
Representation of analog RAD-AI4-IFS values
Analog RAD-AO4-IFS outputs
Table 9-7
Representation of analog RAD-AO4-IFS values
Analog RAD-DAIO6-IFS and RAD-900-DAIO6 inputs and outputs
Table 9-8
Representation of analog RAD-DAIO6-IFS values
Data word
hex
dec/error code
0 mA ... 20 mA
4 mA ... 20 mA
0000
0
0 mA
-
1770
6000
4 mA
4 mA
7530
30000
20 mA
20 mA
7F00
32512
21.67 mA
21.67 mA
8001
Overrange
>21.67 mA
>21.67 mA
8002
Open circuit
-
<3.2 mA
8080
Underrange
< 0 mA
-
Data word
hex
dec/error code
0 mA ... 20 mA
0 V ... 10 V
0000
0
0 mA
0 V
7530
30000
20 mA
10 V
7F00
32512
21.67 mA
10.84 V
Data word
hex
dec/error code
0 ... 20 mA
4 ... 20 mA
0 V ... 10 V
0000
0
0 mA
-
0 V
1770
6000
4 mA
4 mA
2 V
7530
30000
20 mA
20 mA
10 V
7F00
32512
21.67 mA
21.67 mA
10.84 V
8001
Overrange
>21.67 mA
>21.67 mA
-
8002
Open circuit
-
<3.2 mA
-
8080
Underrange
<0 mA
-
-