Connecting devices to IOL MA8 PN DI8 ports
Figure 3-5
SIO connection
The following provides information about the power supply ports.
Connecting IO-Link devices
Use the following procedure to connect IO-Link devices to an IO-Link port.
1.
Insert the IO-Link device negative wire into the L- position until the wire is fully secure.
2.
Insert the IO-Link device positive wire into the L+ position until the wire is fully secure.
3.
If applicable, insert the digital input signal wire into the DI position until the wire is fully
secure.
4.
Insert the IO-Link wire into the C/Q position until the wire is fully secure.
5.
If necessary, configure IO-Link parameters for each port.
Connecting digital input devices to IOL MA8 PN DI8 ports
Use the following procedure to connect a digital input device to an IO-Link port.
1.
Insert the IO-Link device negative wire into the L- position until the wire is fully secure.
2.
Insert the IO-Link device positive wire into the L+ position until the wire is fully secure.
3.
Insert the digital input signal wire into the DI position until the wire is fully secure.
Table 3-1
Power supply port connections
Label
Signal
Description
Value
1
L+
Power supply output (+)
200 mA @ 24 V
(Maximum)
2
L-
Power supply output (-)
3
DI
Digital input
Not applicable
4
C/Q
Communication signal, which supports
SDCI (IO-Link) or SIO (standard
input/output)
200 mA @ 24 V
(Maximum)
L+
L-
DI
C/Q
IO-Link
SIO
It may be useful to remove the plug-in terminal block from the IOL MA8 PN DI8 to aid in
wire termination.