The Inline controller under PC Worx
6959_en_07
PHOENIX CONTACT
57
Table 3-8
FILE_SEEK function block inputs and outputs
Name
Data
type
Data direction
Description
Execute
BOOL
Input
Rising edge: block sets the new position of the file pointer.
Handle
UINT
Input
File handle of file in which the position is to be set.
Position
DINT
Input
New position in the file.
Mode
UINT
Input
Positioning mode
0:
Positioning relative to start of file.
1:
Positioning relative to current position.
2:
Positioning relative to end of file.
Done
BOOL
Output
FALSE:
The function block was not executed.
TRUE:
The function block was executed.
Error
BOOL
Output
FALSE:
No errors occurred when setting the position.
TRUE:
An error occurred when setting the position.
ErrorID
UINT
Output
Error number of the error that occurred when setting the position:
0:
No error information available.
1:
Invalid file handle.
13:
Invalid positioning mode.
24:
The position could not be set.