Diagnostic messages for parameter errors
7619_en_05
PHOENIX CONTACT
B 3
Diagnostic messages for parameter errors
B 3.1
Diagnostic messages for F-Parameters and iParameters
for PROFIsafe
Table B-2
F-Parameter parameter errors
Error code
Error cause
Remedy
dec
hex
64
40
The parameterized F_Destination_Address does not
match the PROFIsafe address set on the safety module
(F-Module).
Match the PROFIsafe address of the safety
module and the value in F_Destination_Ad-
dress.
65
41
Invalid parameterization of F_Destination_Address.
Addresses 0000
hex
and FFFF
hex
are not permitted.
Correct value.
66
42
Invalid parameterization of F_Source_Address.
Addresses 0000
hex
and FFFF
hex
are not permitted.
Correct value.
67
43
Invalid parameterization of F_WD_Time.
A monitoring time of 0 ms is not permitted.
Correct value.
68
44
Invalid parameterization of F_SIL.
The safety module (F-Module) cannot support the re-
quired SIL.
Use a device with the required SIL.
The safety module achieves SIL 3, maximum.
69
45
Invalid parameterization of F_CRC_Length.
The CRC length generated by the safety module (F-
Module) does not match the required length.
Check device description.
70
46
Invalid F-Parameter record version.
The safety module (F-Module) version does not match
the required version.
Check device description.
Only V2 mode permitted.
71
47
The checksum determined by the safety module (F-
Module) via the PROFIsafe parameters (CRC1) does not
match the CRC1 transmitted in the parameter telegram.
Check F-Parameters, repeat calculation.
255
FF
During active process data communication, a new F-Pa-
rameter block was received, which differs from the F-Pa-
rameter block currently used.
Only send modified parameter data when pro-
cess data communication is not active.
Incorrect type ID for the F-Parameter block (F_-
Block_ID).
Check device description.
Summary of Contents for IB IL 24 PSDO 8-PAC
Page 1: ...User manual IB IL 24 PSDO 8 PAC Inline module with safe digital outputs...
Page 16: ...IB IL 24 PSDO 8 PAC 16 112 PHOENIX CONTACT 7619_en_05...
Page 32: ...IB IL 24 PSDO 8 PAC 32 112 PHOENIX CONTACT 7619_en_05...
Page 38: ...IB IL 24 PSDO 8 PAC 38 112 PHOENIX CONTACT 7619_en_05...
Page 54: ...IB IL 24 PSDO 8 PAC 54 112 PHOENIX CONTACT 7619_en_05...
Page 68: ...IB IL 24 PSDO 8 PAC 68 112 PHOENIX CONTACT 7619_en_05...
Page 78: ...IB IL 24 PSDO 8 PAC 78 112 PHOENIX CONTACT 7619_en_05...
Page 80: ...IB IL 24 PSDO 8 PAC 80 112 PHOENIX CONTACT 7619_en_05...
Page 90: ...IB IL 24 PSDO 8 PAC 90 112 PHOENIX CONTACT 7619_en_05...
Page 106: ...IB IL 24 PSDO 8 PAC 106 112 PHOENIX CONTACT 7619_en_05...