Technical data and ordering data
7619_en_05
PHOENIX CONTACT
10.3
Conformance with EMC Directive
Safe digital outputs OUT0 to OUT3 (Fortsetzung)
WARNING: Loss of safety function
–
Connect the ground of the actuator directly to the ground terminal point of the corresponding output on the
Inline plug. Use of an external ground is not permissible.
–
The connected load must not respond in a hazardous way to test pulses.
Electrical isolation / Isolation of the voltage ranges
Separate potentials in the system consisting of bus coupler/power terminal and safety module
- Test distance
- Test voltage
5 V supply of incoming remote bus / 7.5 V supply (bus logic)
500 V AC, 50 Hz, 1 min.
5 V supply of outgoing remote bus / 7.5 V supply (bus logic)
500 V AC, 50 Hz, 1 min.
7.5 V supply (bus logic) / 24 V supply U
M
, FE
500 V AC, 50 Hz, 1 min.
To provide electrical isolation between the logic level and the I/O area, it is necessary to supply the bus coupler
and this safety module from separate power supply units. Interconnection of the power supply units in the 24 V
area is not permitted. (See also user manual.)
Approvals
For the latest approvals, please visit
.
Conformance with EMC Directive 2014/30/EU
Noise immunity test according to DIN EN 61000-6-2
Electrostatic discharge (ESD)
EN 61000-4-2
(IEC 61000-4-2)
Criterion B
6 kV contact discharge, 8 kV air discharge
Electromagnetic fields
EN 61000-4-3
(IEC 61000-4-3)
Criterion A, field strength 10 V/m
Fast transients (burst)
EN 61000-4-4
(IEC 61000-4-4)
Criterion B, test voltage 2 kV
Transient overvoltage (surge)
EN 61000-4-5
(IEC 61000-4-5)
Test intensity 2, Criterion B
DC supply lines:
0.5 kV/0.5 kV (symmetrical/asymmetrical)
Signal lines:
1.0 kV/2.0 kV (symmetrical/asymmetrical)
Conducted disturbance variables
EN 61000-4-6
(IEC 61000-4-6)
Criterion A; test voltage: 10 V
Noise emission test according to DIN EN 61000-6-4
Noise emission
EN 55011
Class A Industrial
Summary of Contents for IB IL 24 PSDO 8-PAC
Page 1: ...User manual IB IL 24 PSDO 8 PAC Inline module with safe digital outputs...
Page 16: ...IB IL 24 PSDO 8 PAC 16 112 PHOENIX CONTACT 7619_en_05...
Page 32: ...IB IL 24 PSDO 8 PAC 32 112 PHOENIX CONTACT 7619_en_05...
Page 38: ...IB IL 24 PSDO 8 PAC 38 112 PHOENIX CONTACT 7619_en_05...
Page 54: ...IB IL 24 PSDO 8 PAC 54 112 PHOENIX CONTACT 7619_en_05...
Page 68: ...IB IL 24 PSDO 8 PAC 68 112 PHOENIX CONTACT 7619_en_05...
Page 78: ...IB IL 24 PSDO 8 PAC 78 112 PHOENIX CONTACT 7619_en_05...
Page 80: ...IB IL 24 PSDO 8 PAC 80 112 PHOENIX CONTACT 7619_en_05...
Page 90: ...IB IL 24 PSDO 8 PAC 90 112 PHOENIX CONTACT 7619_en_05...
Page 106: ...IB IL 24 PSDO 8 PAC 106 112 PHOENIX CONTACT 7619_en_05...